| Plan Review Notes For Permit 16120958 |
| Permit Number |
16120958 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-31 08:13:53 | 1) INDICATE ON THE SITE PLAN IF THE IRRIGATION SYSTEM | | | IS CONNECTED TO THE DOMESTIC WATER SERVICE LINE OR IF | | | THERE IS GOING TO BE A SEPARATE METER & WATER SERVICE | | | FOR THE IRRIGATION SYSTEM.IF A SEPARATE METER AND WATER | | | SERVICE IS TO BE PROVIDED, THE LOCATION OF THE BACKFLOW | | | DEVICE SHALL BE AS CLOSE TO THE METER AS POSSIBLE. | | | CONTACT CITY OF WPB UTILITIES AT 561-822-2240 FOR | | | DIRECTION ON LOCATION REQUIREMENTS FOR THE BACKFLOW | | | DEVICE. | | | 2) SUBMIT TWO COPIES OF MANUF. SPECIFICATIONS FOR THE | | | BACKFLOW DEVICE. THE DEVICE SHALL BE LEAD FREE PER CWPB | | | CROSS-CONNECTION CONTROL MANUAL. | | | 3) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FROM A | | | LICENSED PLUMBING CONTRACTOR TO PROVIDE A CONNECTION | | | AND INSTALL THE BACKFLOW PREVENTER ON THE SYSTEM. THE | | | IRRIGATION CONTRACTOR SHALL CONNECT THE IRRIGATION | | | SYSTEM TO THE OUTLET OF THE BACKFLOW PREVENTER. AN | | | IRRIGATION LICENSE DOES NOT PERMIT THE IRRIGATION | | | CONTRACTOR TO CONNECT TO THE POTABLE WATER SYSTEM. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|