| Plan Review Notes For Permit 16120953 |
| Permit Number |
16120953 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-04 17:34:37 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120953 | | | 5/4/17 | | | | | | 1) THE ENERGYGAUGE FORM R405-2014 AND AC CALCULATIONS | | | ARE BOTH INDICATING A THOUGH-THE WALL 1-TON AC SYSTEM | | | AT 15 SEER, HOWEVER THE PLANS ARE INDICATING A 2-TON | | | SPLIT SYSTEM. | | | | | | 2) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE | | | GOODMAN AIR HANDLER TO VERIFY IT CAN PRODUCE 1000 CFMS | | | OF SUPPLY AIR AS INDICATED ON THE PLAN. | | | | | | 3) PROVIDE THE DIMENSIONS OF THE AC DUCT DROP FROM THE | | | 2ND TO THE 1ST FLOOR. | | | | | | 4) CLARIFY HOW AIR IS BEING RETURNED TO THE AIR HANDLER | | | ON THE 2ND FLOOR. THERE IS NO RETURN GRILL SHOWN AND | | | THE DOOR IS INDICATED TO BE SOLID IN THE DOOR SCHEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|