2017-05-04 17:34:372ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120953
 5/4/17
  
 1) THE ENERGYGAUGE FORM R405-2014 AND AC CALCULATIONS
 ARE BOTH INDICATING A THOUGH-THE WALL 1-TON AC SYSTEM
 AT 15 SEER, HOWEVER THE PLANS ARE INDICATING A 2-TON
 SPLIT SYSTEM.
  
 2) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 GOODMAN AIR HANDLER TO VERIFY IT CAN PRODUCE 1000 CFMS
 OF SUPPLY AIR AS INDICATED ON THE PLAN.
  
 3) PROVIDE THE DIMENSIONS OF THE AC DUCT DROP FROM THE
 2ND TO THE 1ST FLOOR.
  
 4) CLARIFY HOW AIR IS BEING RETURNED TO THE AIR HANDLER
 ON THE 2ND FLOOR. THERE IS NO RETURN GRILL SHOWN AND
 THE DOOR IS INDICATED TO BE SOLID IN THE DOOR SCHEDULE.
  