2017-01-05 07:55:231ST REVIEW FBC-2014 RESIDIENTIAL MECHANICAL
 PERMIT #16120953
 1/5/17
  
 1) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS
 INDICATING MAKES, MODELS, COOLING AND HEATING
 CAPACITIES, AND EFFICIENCY RATINGS. THE SUBMIITTED AC
 AND ENERGY CALCULATIONS CANNOT BE REVIEWED IN ENTIRETY
 WITHOUT SYSTEMS' INFORMATION. PLEASE NOTE THAT THE
 SYSTEM IS LISTED AS "GENERIC" UNDER THE EQUIPMENT
 SUMMARY ON THE AC CALCULATIONS.
  
 2) THE COOLING AND HEATING SYSTEM COMPLIANCE DATA ON
 THE SUBMITTED ENERGYGAUGE FORM R405-2014 DOES NOT MATCH
 THE PLANS: A) THE THROUGH THE WALL SYSTEMS SHOWN ON THE
 PLAN ARE LISTED AS ONE "CENTRAL UNIT" ON THE FORM. B)
 THE REVERSE CYCLE HEATING SYSTEMS SHOWN ON THE PLAN ARE
 LISTED AS HEAT STRIPS ON THE FORM.
  
 3) THE ENERGYGAUGE FORM MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 4) THE PLANS MUST BE REVISED TO SHOW THE INSULATION
 R-VALUES IN THE WALLS AND CEILING IN ORDER TO VERIFY
 THE VALUES LISTED ON THE ENERGY FORM R405-2014 ARE
 ACCURATE.
  
 5) THE ENERGY FORM R405 IS LISTING EITHER NEW OR
 EXISTING DOUBLE-PANED WINDOWS AT 0.29 U-FACTOR/0.23
 SHGC. PLEASE PROVIDE A WINDOW SCHEDULE ON THE PLAN AND
 SUBMIT MANUFACTURER'S DATA SHEET FOR REVIEW.
  
 6) PROVIDE A DRYER VENTING PLAN.
  