| 2017-01-05 07:55:23 | 1ST REVIEW FBC-2014 RESIDIENTIAL MECHANICAL |
| | PERMIT #16120953 |
| | 1/5/17 |
| | |
| | 1) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS |
| | INDICATING MAKES, MODELS, COOLING AND HEATING |
| | CAPACITIES, AND EFFICIENCY RATINGS. THE SUBMIITTED AC |
| | AND ENERGY CALCULATIONS CANNOT BE REVIEWED IN ENTIRETY |
| | WITHOUT SYSTEMS' INFORMATION. PLEASE NOTE THAT THE |
| | SYSTEM IS LISTED AS "GENERIC" UNDER THE EQUIPMENT |
| | SUMMARY ON THE AC CALCULATIONS. |
| | |
| | 2) THE COOLING AND HEATING SYSTEM COMPLIANCE DATA ON |
| | THE SUBMITTED ENERGYGAUGE FORM R405-2014 DOES NOT MATCH |
| | THE PLANS: A) THE THROUGH THE WALL SYSTEMS SHOWN ON THE |
| | PLAN ARE LISTED AS ONE "CENTRAL UNIT" ON THE FORM. B) |
| | THE REVERSE CYCLE HEATING SYSTEMS SHOWN ON THE PLAN ARE |
| | LISTED AS HEAT STRIPS ON THE FORM. |
| | |
| | 3) THE ENERGYGAUGE FORM MUST BE SIGNED AND DATED BY THE |
| | OWNER/AGENT. |
| | |
| | 4) THE PLANS MUST BE REVISED TO SHOW THE INSULATION |
| | R-VALUES IN THE WALLS AND CEILING IN ORDER TO VERIFY |
| | THE VALUES LISTED ON THE ENERGY FORM R405-2014 ARE |
| | ACCURATE. |
| | |
| | 5) THE ENERGY FORM R405 IS LISTING EITHER NEW OR |
| | EXISTING DOUBLE-PANED WINDOWS AT 0.29 U-FACTOR/0.23 |
| | SHGC. PLEASE PROVIDE A WINDOW SCHEDULE ON THE PLAN AND |
| | SUBMIT MANUFACTURER'S DATA SHEET FOR REVIEW. |
| | |
| | 6) PROVIDE A DRYER VENTING PLAN. |
| | |