| Date |
Text |
| 2017-05-09 17:39:11 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ROOF TILE SELF-ADHERED UNDERLAYMENT AS SPECIFIED ON |
| | PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) FLAT ROOF AS SHOWN ON PLANS FOR GARAGE AND ROOF DECK |
| | ABOVE FRONT PORCH. AND CLEARLY IDENTIFY WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE USED. AND, PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE CALCULATED DESIGN PRESSURES. NOTE: |
| | VERIFY THAT SELECTED ASSEMBLY ALLOWS FOR RAS 117 |
| | CALCULATIONS. |
| | RESPONSE: REPEAT COMMENT. THERE ARE TWO DIFFERENT |
| | PRODUCT APPROVALS SUBMITTED: FLORIDA PRODUCT APPROVAL |
| | FL16709 AND NOA 13-1217.01. CLARIFY WHICH ONE IS GOING |
| | TO BE USED IN THIS PROJECT. OR IF USING BOTH, THEN |
| | CLEARLY SPECIFY WHERE EACH PRODUCT APPROVAL IS GOING TO |
| | BE INSTALLED: GARAGE OR MAIN HOUSE ROOF DECK ABOVE |
| | FRONT PORCH. NOTES: (1) IT'S NOT CLEAR WHY SEVERAL |
| | ASSEMBLIES WHERE MARKED ON FLORIDA PRODUCT APPROVAL |
| | FL16709-R3. CLEARLY IDENTIFY WHICH ONE IS GOING TO BE |
| | USED. (2) DEPENDING ON ASSEMBLY SELECTED FROM NOA |
| | 13-1217.01 SIGNED AND SEALED RAS 117 CALCULATIONS MAY |
| | BE REQUIRED. |
| | |
| | C) RIDGE VENT FOR CONCRETE TILES AS SPECIFIED ON PLANS. |
| | |
| | 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |