| 2017-03-17 11:24:13 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ROOF TILE AS SHOWN ON PLANS |
| | RESPONSE: CLARIFY ROOF TILE ATTACHMENT. USING |
| | NAILS/SCREWS OR ADHESIVE. CLARIFY WHY FLORIDA PRODUCT |
| | APPROVAL FL7804-R9 SUBMITTED IS HIGHLIGHTED ON PAGE 7 |
| | OF 9 WITH A MECHANICALLY FASTENED ATTACHMENT METHOD AND |
| | WHY SUBMITTING A PRODUCT APPROVALS FOR ROOF TILE |
| | ADHESIVE. IF USING , NAILS/SCREWS, THEN ENGINEER OF |
| | RECORD TO SPECIFY SIZE AND NUMBER OF SCREWS. SEC. |
| | 107.2.1.2 CITY AMENDMENTS AND R301.1 FBC-RESIDENTIAL. |
| | |
| | B) ROOF TILE SELF-ADHERED UNDERLAYMENT AS SPECIFIED ON |
| | PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | C) FLAT ROOF AS SHOWN ON PLANS FOR GARAGE AND ROOF DECK |
| | ABOVE FRONT PORCH. AND CLEARLY IDENTIFY WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE USED. AND, PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| | DOESN'T MEET THE CALCULATED DESIGN PRESSURES. NOTE: |
| | VERIFY THAT SELECTED ASSEMBLY ALLOWS FOR RAS 117 |
| | CALCULATIONS. |
| | RESPONSE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS |
| | SUBMITTED: FLORIDA PRODUCT APPROVAL FL16733-R3 AND NOA |
| | 13-0409.09. CLARIFY WHICH ONE IS GOING TO BE USED IN |
| | THIS PROJECT. OR IF USING BOTH, THEN CLEARLY SPECIFY |
| | WHERE IS EACH PRODUCT APPROVAL GOING TO BE INSTALLED: |
| | GARAGE OR MAIN HOUSE ROOF DECK ABOVE FRONT PORCH. |
| | NOTES: (1) SELECTED ASSEMBLY W-8 FROM FLORIDA PRODUCT |
| | APPROVAL FL16733-R3 REQUIRES SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCEMENT AT PERIMETER AND |
| | CORNER AREAS. PROVIDE SUCH CALCULATIONS. (2) NONE OF |
| | THE ASSEMBLIES SUBMITTED WITH NOA 13-0409.09 CAN BE |
| | USED BECAUSE THEY ARE LIMITED BY GENERAL LIMITATION #9. |
| | GENERAL LIMITATION #9 DOESN'T ALLOW RAS 117 |
| | CALCULATIONS. NEED TO SELECT ASSEMBLY THAT IS LIMITED |
| | BY GENERAL LIMITATION #7 AND NEED TO PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301.1 FB-RESIDENTIAL. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: NOT ALL THE PRODUCT APPROVALS WERE REVIEWED |
| | BY THE ENGINEER OF RECORD. SOME PRODUCT APPROVALS WERE |
| | LEFT OUT WITHOUT THE ENGINEER'S APPROVAL. ENGINEER OF |
| | RECORD TO APPROVE IN WRITING EACH PRODUCT APPROVAL |
| | SUBMITTED. |
| | |