| 2017-01-09 14:18:23 | JOB PERMIT NUMBER: 16120944 |
| | JOB ADDRESS: 170 GREENWOOD |
| | WEST PALM BEACH FLORIDA |
| | DATE: JANUARY 3, 2017 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, |
| | (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY |
| | OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF |
| | ITEMS NOTED. |
| | |
| | 1] PROVIDE A/C HEATER SIZE TO VERIFY BREAKER SIZE OF |
| | THE AIR HANDLER UNIT. FBC 107 |
| | |
| | 2] TYPICALLY THE DISHWASHER & DISPOSAL SHOULD BE ON A |
| | DEDICATED INDIVIDUAL BRANCH CIRCUIT, REFER TO FBC-R |
| | SECTION E3702.3 (NEC 210.23(A)(2)) WHICH STATES THE |
| | APPLIANCE FASTENED IN PLACE SHALL NOT EXCEED 50% OF THE |
| | BRANCH CIRCUIT RATING. SHOW COMPLIANCE. |
| | |
| | 3] 75% OF PERMANENT OF PERMANENT LUMINAIRES SHALL BE |
| | HIGH EFFICIENT. FBC-ENERGY SECTION R404.1 A NOTE WILL |
| | SUFFICE. |
| | |
| | 4] RECESSED LIGHTS INSTALLED IN BUILDING ENVELOPE SHALL |
| | BE SEALED TO PREVENT AIR LEAKAGE BETWEEN CONDITIONED & |
| | UN-CONDITIONED SPACES. IN ADDITION IF THE HOUSING CANS |
| | INSTALLED IN THERMAL INSULATION SHALL BE LISTED |
| | IC-RATED. FBC-ENERGY SECTION 402.4.4 A NOTE WILL |
| | SUFFICE. |
| | |
| | 5] ADD AN INTERSYSTEM BONDING TERMINAL TO THE RISER |
| | DIAGRAM GROUNDING DETAIL. FBC-R SECTION E3609.3 SHOW |
| | COMPLIANCE. |
| | |
| | 6] GARAGE ELECTRICAL PLAN REFLECT A 150 AMP PANEL & |
| | RISER DIAGRAM SHOWS 125 AMP PANEL, PLEASE MATCH |
| | ACCORDINGLY. FBC 107 |
| | |
| | 7] PROVIDE CIRCUIT DESIGNATION ON FLOOR PLAN & IDENTIFY |
| | EACH SPACE FOR THE PURPOSE IT SERVES. FBC 107 |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |