| 2017-06-09 13:46:45 | RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS |
| | REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE |
| | PLAN REVIEW REJECTIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- SIZE OF WINDOWS SPECIFIED FOR BEDROOM #3 DON'T SEEM |
| | TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE SIZE OF |
| | WINDOWS OR PROVIDE PROOF THAT SPECIFIED SIZE WILL |
| | COMPLY WITH THE EGRESS REQUIREMENTS. |
| | RESPONSE: REPEAT COMMENT. 4'-5" X 4'-6" WINDOWS DON'T |
| | COMPLY WITH THE EGRESS REQUIREMENTS. THEY DON'T MEET |
| | THE MIN. 24" CLEAR OPENING HEIGHT. REVISE AS REQUIRED. |
| | NOTE: CALLED PGT WINDOWS. THEY SAID THE MINIMUM WINDOW |
| | HEIGHT REQUIRED IS 61.750" (59.5") AND IS FOR A SPECIAL |
| | WINDOW WITH THE EGRESS HEIGHT SPECIFICATION. FOR |
| | EXAMPLE SH25"EH". |
| | |
| | ORIGINAL COMMENT: |
| | 2- PLANS WERE REVISED AND NOW THEY SHOW REPLACEMENT OF |
| | ALL EXISTING WINDOWS AND DOORS. CLEARLY SPECIFY TYPE |
| | AND SIZE OF EXISTING BEDROOM WINDOWS TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704 |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. 4'-5" X 4'-6" WINDOWS DON'T |
| | COMPLY WITH THE EGRESS REQUIREMENTS. THEY DON'T MEET |
| | THE MIN. 24" CLEAR OPENING HEIGHT. REVISE AS REQUIRED. |
| | NOTE: CALLED PGT WINDOWS. THEY SAID THE MINIMUM WINDOW |
| | HEIGHT REQUIRED IS 61.750" (59.5") AND IS FOR A SPECIAL |
| | WINDOW WITH THE EGRESS HEIGHT SPECIFICATION. FOR |
| | EXAMPLE SH25"EH". |
| | |
| | |
| | NOTE: |
| | PLANS WILL NEED TO BE SEND FOR HISTORIC REVIEW ONCE THE |
| | EGRESS WINDOWS ARE REVISED ON PLANS AND ELEVATIONS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |