Plan Review Notes
Plan Review Notes For Permit 16120942
Permit Number 16120942
Review Stop B
Sequence Number 3
Notes
Date Text
2017-05-01 10:18:59RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ARCHITECT TO PAY FOUR TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR MULTIPLE
 PLAN REVIEW REJECTIONS.
  
 1- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM.
 BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- A) SIZE OF WINDOWS SPECIFIED FOR BEDROOM #3 DON'T
 SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE SIZE
 OF WINDOWS OR PROVIDE PROOF THAT SPECIFIED SIZE WILL
 COMPLY WITH THE EGRESS REQUIREMENTS.
 RESPONSE: REPEAT COMMENT. ARCHITECT TO PAY FOUR TIMES
 THE PLAN REVIEW FEE AS REQUIRED BY FLORIDA STATUTE
 553.80(2)(B) FOR MULTIPLE PLAN REVIEW REJECTIONS.
  
 3- PLANS WERE REVISED AND NOW THEY SHOW REPLACEMENT OF
 ALL EXISTING WINDOWS AND DOORS. CLEARLY SPECIFY TYPE
 AND SIZE OF EXISTING BEDROOM WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 704
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
 ARCHITECT DIDN'T SPECIFY TYPE AND SIZE OF EXISTING
 WINDOWS. PROPOSED WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS REQUIREMENTS. UNABLE TO VERIFY THE EGRESS
 REQUIREMENTS.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW WINDOW AND EXTERIOR DOORS FRAMING DETAILS AND THE
 INFILL OF EXTERIOR WALLS BY BEDROOM #3 AND BY THE
 DINING AREA. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING
 COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON
 THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 6- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER NAME AND BUILDER NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ATTIC INFORMATION ON PAGE 3 OF 5 IS CONSIDERING A
 VENT RATIO OF 1/300. TYPICALLY THE VENT RATIO REQUIRED
 BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE CONDITIONS REQUIRED BY
 THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL TO
 CONSIDER THE 1/300 VENTILATION RATIO OR REVISE THE
 VENTILATION RATIO AS REQUIRED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 7- DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE
 1/300 VENTILATION RATIO AS SPECIFIED ON THE ENERGY
 CALCULATIONS ON PAGE 3 OF 5. COORDINATE WITH THE ENERGY
 CALCULATIONS SUBMITTED. NOTE: TYPICALLY THE VENT RATIO
 REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THE EXISTING HOUSE COMPLIES WITH THE CONDITIONS
 REQUIRED BY THE EXCEPTION ON SEC. R806.2
 FBC-RESIDENTIAL TO CONSIDER THE 1/300 VENTILATION
 RATIO.
 RESPONSE: ENERGY CALCULATIONS DIDN'T REVISED THE
 VENTILATION RATIO. THAT'S WHY THIS INFORMATION IS
 REQUIRED.
  
 8- SCOPE OF WORK WAS REVISED. UPDATE VALUATION TO
 INCLUDE ALL THE ADDITIONAL WORK INCLUDING WINDOW /DOORS
 REPLACEMENT, NEW ROOF TILE, ETC AND ALL THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CUSTOM ENTRY DOOR AS SPECIFIED ON PLANS. NOTE:
 DRAWING #ET0003 SUBMITTED IS NOT AN APPROVED FLORIDA
 PRODUCT APPROVAL OR MIAMI-DADE NOA. IF THERE IS NO
 OFFICIAL PRODUCT APPROVAL, THEN MANUFACTURER MAY SUBMIT
 COMPLETE ORIGINAL ENGINEERING PACKAGE FOR LOCAL PRODUCT
 APPROVAL. THIS WILL BE REVIEWED AND APPROVE BY THE
 BUILDING OFFICIAL. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) FRENCH DOORS. ONLY ONE COPY WAS SUBMITTED. NEED TO
 PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) SINGLE HUNG WINDOWS. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) CONCRETE ROOF TILE. ONLY ONE COPY WAS SUBMITTED.
 NEED TO PROVIDE 2 COPIES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 E) ROOF TILE ADHESIVE AS SPECIFIED BY THE ARCHITECT OF
 RECORD ON COVER PAGE OF NOA SUBMITTED. SEE NOA FOR
 LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 10- ARCHITECT OF RECORD TO REVIEW ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
 11- ARCHITECT TO CLARIFY WHAT ARE THE THREE ADDITIONAL
 LINES SHOWN IN THE WALL BY THE NEW MASTER BEDROOM
 CLOSET. PROVIDE WALL LEGEND. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  