2017-03-27 19:15:09RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS.
 A) ONLY THE EQUIPMENT SIZING SUMMARY WAS SUBMITTED.
 NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING
 CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) MASTER BEDROOM NEEDS TO COMPLY WITH THE BALANCED
 RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION
 (2014). NOTE: ALL THE SUPPLY AIR INTO THE MASTER
 BEDROOM SHALL BE INCLUDED. THIS INCLUDES MASTER BATH
 AND CLOSET. SEE EXCEPTION #3 OF SEC. M1602.4 AND REVISE
 THE SIZE OF THE TRANSFER DUCT SPECIFIED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  