| 2017-03-27 19:15:09 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS. |
| | A) ONLY THE EQUIPMENT SIZING SUMMARY WAS SUBMITTED. |
| | NEED TO PROVIDE THE COMPLETE EQUIPMENT SIZING |
| | CALCULATIONS. SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE |
| | HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR |
| | PUBLIC RECORDS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) MASTER BEDROOM NEEDS TO COMPLY WITH THE BALANCED |
| | RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). NOTE: ALL THE SUPPLY AIR INTO THE MASTER |
| | BEDROOM SHALL BE INCLUDED. THIS INCLUDES MASTER BATH |
| | AND CLOSET. SEE EXCEPTION #3 OF SEC. M1602.4 AND REVISE |
| | THE SIZE OF THE TRANSFER DUCT SPECIFIED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |