| 2017-03-27 15:17:38 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROPOSED PLANS SHOW CONVERSION OF GARAGE TO BEDROOM. |
| | AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH COUNTY |
| | (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING |
| | BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF |
| | FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- SPECIFY TYPE AND SIZE OF WINDOW FOR BEDROOM #3 TO |
| | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| | R310 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: NONE OF THE WINDOW SIZES SHOWN ON BEDROOM #3 |
| | COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). ALSO, WINDOW |
| | SCHEDULE DOESN'T SPECIFY TYPE OF WINDOW. REVISE AS |
| | REQUIRED. PROVIDE COMPLETE INFORMATION. |
| | |
| | 3- NEW COMMENT. PLANS WERE REVISED AND NOW THEY SHOW |
| | REPLACEMENT OF ALL EXISTING WINDOWS AND DOORS. CLEARLY |
| | SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS TO |
| | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| | 704 FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW WINDOW AND EXTERIOR DOORS FRAMING DETAILS AND THE |
| | INFILL OF EXTERIOR WALLS BY BEDROOM #3 AND BY THE |
| | DINING AREA. SPECIFY ALL FRAMING MEMBERS AND |
| | CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | EXISTING GARAGE EXTERIOR WALLS AND CEILING SHOWING |
| | COMPLIANCE WITH THE INSULATION REQUIREMENTS SHOWN ON |
| | THE ENERGY CALCULATIONS. SEC. R103.2 FBC-ENERGY |
| | CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 6- ENERGY CALCULATIONS SUBMITTED; |
| | A) OWNER NEEDS TO CERTIFY AT BOTTOM OF FORM AS REQUIRED |
| | BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | RESPONSE: CLARIFY WHY THE SIGNATURE OF THE OWNER IS NOT |
| | THE SAME AS THE SIGNATURE SHOWN ON THE PERMIT |
| | APPLICATION. |
| | |
| | B) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO |
| | PROVIDE HIS NAME, LICENSE NUMBER, ETC AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE OWNER NAME AND BUILDER NAME. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D) NEW COMMENT: FLOOR PLANS WERE REVISED. ENERGY |
| | CALCULATIONS NEED TO BE REVISED REFLECTING THE SQUARE |
| | FOOTAGE OF REVISED PLANS. |
| | |
| | E) ATTIC INFORMATION ON PAGE 3 OF 5 IS CONSIDERING A |
| | VENT RATIO OF 1/300. TYPICALLY THE VENT RATIO REQUIRED |
| | BY SEC. R806.2 FBC-RESIDENTIAL IS 1/150. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| | EXISTING HOUSE COMPLIES WITH THE CONDITIONS REQUIRED BY |
| | THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL TO |
| | CONSIDER THE 1/300 VENTILATION RATIO. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | F) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED |
| | BY SEC. R405.4.3 FBC-ENERGY CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 7- SCOPE OF WORK WAS REVISED. UPDATE VALUATION TO |
| | INCLUDE ALL THE ADDITIONAL WORK INCLUDING WINDOW /DOORS |
| | REPLACEMENT, NEW ROOF TILE, ETC AND ALL THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) CUSTOM ENTRY DOOR AS SPECIFIED ON PLANS. NOTE: |
| | DRAWING #ET0003 SUBMITTED IS NOT AN APPROVED FLORIDA |
| | PRODUCT APPROVAL OR MIAMI-DADE NOA. IF THERE IS NO |
| | OFFICIAL PRODUCT APPROVAL, THEN MANUFACTURER MAY SUBMIT |
| | COMPLETE ORIGINAL ENGINEERING PACKAGE FOR LOCAL PRODUCT |
| | APPROVAL. THIS WILL BE REVIEWED AND APPROVE BY THE |
| | BUILDING OFFICIAL. ONLY ONE COPY WAS SUBMITTED. NEED TO |
| | PROVIDE 2 COPIES. |
| | |
| | B) FRENCH DOORS. ONLY ONE COPY WAS SUBMITTED. NEED TO |
| | PROVIDE 2 COPIES. |
| | |
| | C) SINGLE HUNG WINDOWS. ONLY ONE COPY WAS SUBMITTED. |
| | NEED TO PROVIDE 2 COPIES. |
| | |
| | D) CONCRETE ROOF TILE. ONLY ONE COPY WAS SUBMITTED. |
| | NEED TO PROVIDE 2 COPIES. |
| | |
| | E) ROOF TILE ADHESIVE AS SPECIFIED BY THE ARCHITECT OF |
| | RECORD ON COVER PAGE OF NOA SUBMITTED. SEE NOA FOR |
| | LISTED ADHESIVES. |
| | |
| | F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES. |
| | |
| | 9- ARCHITECT OF RECORD TO REVIEW ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 10- ARCHITECT TO CLARIFY WHAT ARE THE THREE ADDITIONAL |
| | LINES SHOWN IN THE WALL BY THE NEW MASTER BEDROOM |
| | CLOSET. PROVIDE WALL LEGEND. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |