| 2017-06-07 12:31:14 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16120880 |
| | ADD: 3200 N. CONGRESS / TENNIS CENTER BUILDING |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-308-2954 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: WED. JUNE 07/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) 3RD REQUEST. SEMI-COMPLIED. PLEASE NOTE THE PERMIT |
| | APPLICATION STILL INDICATES 3200 N. CONGRESS. IT IS THE |
| | CONTRACTORS RESPONSIBILITY TO UPDATE THE ADDRESS ON THE |
| | PERMIT APPLICATION. PLEASE ALSO NOTE THE PERMIT SET OF |
| | PLANS NOW INDICATE THE ADDRESS OF 1998 LACELEAF COURT. |
| | THIS APPEARS TO BE A TYPO, IN CONTACTING MR. ORIO, HE |
| | CONFIRMED THE ADDRESS SHOULD READ 1989 LACELEAF COURT. |
| | CITY MUNI CODE SEC.78-6 (1-7). THE SUBMITTED ADDRESS |
| | WILL BE REASSIGNED BY CONTACT: |
| | MICHAEL ORIO GIS SUPPORT SPECIALIST/ INFORMATION |
| | TECHNOLOGY |
| | TEL: 561-494-1040 |
| | E-MAIL: [email protected] |
| | |
| | 2) BUILDING PROVISO: THIS PROJECT QUALIFIES FOR ART IN |
| | PUBLIC PLACES. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 3) 3RD REQUEST. THIS IS A CONTRACTOR ISSUE TO RIGHT |
| | BACK A WRITTEN RESPONSE!!!! THE RESPONSE LETTER WILL |
| | STAND IF NO WRITTEN RESPONSE FROM HEDRICK BROTHERS IN |
| | THE NEXT SET OF COMMENTS. |
| | |
| | THIS PROJECT THE TENNIS CENTER BUILDING IS EVALUATED AT |
| | $783420.00 DOLLARS. UNDER THE MAIN BUILDING PERMIT THE |
| | VALUES FOR THE, GROUNDWATER-DEWATERING, EXCAVATING, |
| | DE-MUCKING AND BACKFILL FOR THE BUILDING, MECHANICAL, |
| | ELECTRICAL, PLUMBING & ROOFING SUB-PERMITS ARE |
| | INCLUDED. PLEASE NOTE THIS REVIEW IS FOR THE BUILDING |
| | ONLY, NOT FOR ANY SITE AMENITIES OR PARKING LOTS. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| | IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR |
| | STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND |
| | ASSOCIATED FEES WITH EACH PERMIT. |
| | |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | |
| | |
| | |
| | 4) SEMI-COMPLIED. THIS REVIEW THE PLANS ARE SIGNED AND |
| | SEALED BUT IN THIS GENERATION OF PLANS THE PLANS DO NOT |
| | PROVIDE NAME OF THE LICENSE HOLDER. 61G1-16.004 TITLE |
| | BLOCK. ARCHITECT. (6) THE PRINTED NAME AND THE |
| | LICENSE/REGISTRATION NUMBER OF THE PERSON SEALING THE |
| | DOCUMENT. |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) 3RD REQUEST. RESPONSE INDICATES THE SURVEY IS TO BE |
| | SUBMITTED UNDER SEPARATE COVER. PLEASE REFER TO; |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1ST ROUND OF COMMENTS. IN THE ARCHITECTURAL SET OF |
| | PLANS THERE IS AN OVERALL MASTER SITE PLAN FOR THE |
| | DEVELOPMENT AND A SITE PLAN. THE CIVIL PLANS SHEET 4 OF |
| | 9 SHOWS THE LOCATION OF THE PROPOSED TENNIS PAVILION, |
| | BUT THERE IS NO SURVEY IN THIS REVIEW CYCLE GIVING THE |
| | LOCATION OF PROPERTY LINES AND THE DISTANCE FROM THE |
| | BUILDING TO SUCH PROPERTY LINES. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | . 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDINGS-SURVEY. |
| | CANNOT VERIFY: |
| | 2014 FBC-B TABLE 602 FIRE-RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPARATION DISTANCE |
| | 2014 FBC-B TABLE 705.8. MAXIMUM AREA OF EXTERIOR WALL |
| | OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| | OF OPENING PROTECTION |
| | |
| | 9) SHEET S-0.00 FOUNDATION NOTES 310000: |
| | |
| | 9A) 3RD REQUEST. THIS COMMENT IS A CONTRACTOR |
| | RESPONSIBILITY!!!RESPONSE INDICATES THAT THE REVISED |
| | GEOTECHNICAL REPORT THAT ADDRESSES THE EXTENT OF THE |
| | ONSITE SOILS ENGINEER TO BE SUBMITTED UNDER SEPARATE |
| | COVER IN RESPONSE TO THIS COMMENT. |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1ST ROUND OF COMMENTS. NOTES INDICATE THAT ALL SOILS |
| | BEARING ARE TO BE INSPECTED & APPROVED BY A |
| | GEOTECHNICAL ENGINEER. IN UNIVERSAL ENGINEERING |
| | GEOTECHNICAL ENGINEERING REPORT SUBMITTED THE SOILS |
| | ENGINEER FOUND IN (3) SOILS SAMPLES ORGANIC SOILS |
| | CONTENTS RANGING FROM 10.6 TO 67.6 PERCENT AND FROM A |
| | DEPTH OF 6 FEET TO 12 FEET BELOW GRADE. WE HAVE NO |
| | DOCUMENTATION FROM THE CONTRACTOR OR SOILS ENGINEER |
| | THERE WILL BE AN ONSITE SOILS ENGINEER DURING THE |
| | REMOVAL OF THE ORGANIC SOILS, AND REPLACED WITH A GOOD |
| | QUALITY FILL ACCORDING TO THE SPECIFICATIONS AND |
| | PROCEDURES OUTLINED IN THE SITE PREPARATION SECTION OF |
| | THE SUBMITTED SOILS REPORT. |
| | BASED ON THE SOILS ENGINEERS RECOMMENDATION FOR |
| | DEWATERING OF THE BUILDING SITE , OVER EXCAVATION, |
| | PLACEMENT OF FILL THERE SHALL BE QUALIFIED PERSONNEL |
| | AND EQUIPMENT TO MONITOR THE DEVELOPMENT OF THE SITE |
| | BUILDING PAD AS DESCRIBED IN SECTION 4.5 OF THIS |
| | REPORT. FBC-B 1803.4 QUALIFIED REPRESENTATIVE & |
| | 1803.5.8 COMPACTED FILL MATERIALS. |
| | |
| | 9B) BUILDING PROVISO, DEFERRED SUBMITAL: CONTRACTOR TO |
| | FURNISH THE DE-WATERING PLAN AND BE REVIEWED BY THE |
| | DESIGN PROFESSIONAL OF RECORD AND THEIR SHOP DRAWING |
| | STAMP OF APPROVAL ON THE DOCUMENT BEFORE BEING |
| | FORWARDED TO THE BUILDING DEPARTMENT. |
| | THE SECOND ISSUE WITH THE PREPARING FOR DE-MUCKING IS A |
| | DE-WATERING PLAN. TO DATE NO PLAN/ REPORT HAS BEEN |
| | SUBMITTED PROVIDING A METHOD OF DEWATERING & |
| | CALCULATIONS FOR THE APPROPRIATE SYSTEM AND ARE THE |
| | SOLE RESPONSIBILITY OF THE CONTRACTOR. DEPENDING ON THE |
| | TIME OF YEAR THE WATER TABLE WOULD BE 2 FT. TO 4 FT. |
| | BELOW GRADE AND ORGANIC MATERIALS WERE FOUND IN BORING |
| | # 3 TO A DEPTH OF 12 FEET BELOW GRADE. THE SUBMITTED |
| | SOILS REPORT REQUEST THAT THE GROUND WATER SHOULD BE |
| | CONTROLLED TO A DEPTH OF AT LEAST 2 FEET BELOW THE |
| | BOTTOM OF THE EXCAVATION DURING THE ENTIRE DEMUCKING |
| | OPERATION. 1803.5.4 GROUND-WATER TABLE. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) BUILDING PROVISO DEFERED SUBMITTAL: THE CONTRACTOR |
| | HEDRICK BROTHER HAS SUBMITTED A REQUEST FOR DEFERRED |
| | SUBMITTALS PER 2014 FLORIDA BUILDING CODE W 2014 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.3.4.2 DEFERRED |
| | SUBMITTALS; |
| | 1) WOOD TRUSSES- SHOP DRAWINGS AND ENGINEERING SHEETS |
| | OF TRUSSES |
| | 2) ALUMINUM LOUVERS |
| | 3) EXTERIOR WINDOWS AND DOORS |
| | 4) ROOFING ASSEMBLIES |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 12)COMPLIED. SHEET A-3. 2014 FBC-ACCESSIBILITY CODE |
| | 404.2.6. |
| | |
| | 13)COMPLIED. 2014 FBC-ENERGY CODE COMMERCIAL BUILDINGS |
| | |
| | 14) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |