| 2017-01-24 09:43:04 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT IS CALLING |
| | THIS PROJECT AN A-2 IT SHOULD BE AN A-3 PLEASE CLARIFY |
| | . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. ARE THE RESTROOMS IN THE TENNIS CENTER SERVING THE |
| | TENNIS COURTS OCCUPANT LOAD IF SO INCLUDE IT IN THE |
| | FIXTURE COUNT IF NOT SHOW LOCATION OF BATHROOMS SERVING |
| | TENNIS COURTS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHOW COMPLIANCE FOR TOILET PAPER DISPENSER PER FBC |
| | ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 4. SHOW COMPLIANCE FOR TOILET . PER FBC ACC 604.2 |
| | LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| | RIGHT-HAND APPROACH. |
| | |
| | 5. SHT. A-1.4.02 GENERAL NOTE AND ADA NOTES ARE UNCLEAR |
| | SOME OF THE WORDS ARE OVERLAPPING PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT. A-1.4.03 NOTES REFERENCE 2010 ADA AND 2012 FABC |
| | THIS PROJECT SHALL BE DESIGNED UNDER FBC ACC 2014 5TH |
| | ADDITION. PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. 1.4.04 IS MISSING WORDS AND FIGURE NUMBERS FOR |
| | EXAMPLE 403.5.2 CLEAR WIDTH AT ?, 404 DOORS DOORWAYS |
| | AND ? AND THE FIGURES ARE MISSING SEC NUMBERS PLEASE |
| | CLARIFY . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1 |
| | AND SHALL COMPLY WITH FBC PL |
| | [B] 410.2 MINIMUM NUMBER. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | AND FBC ACC 602 |
| | |
| | 9. ALL LAVATORY'S ARE REQUIRED TO HAVE TEMPERED WATER. |
| | PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 10. PLEASE PROVIDE NOT ON THE PLAN FOR SEPARATE PERMIT |
| | REQUIRED FOR THE BACKFLOW AT THE METER. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 11. SHUT OFF VALVES ARE REQUIRED ON THE HW FEEDS TO |
| | EACH BATHROOM. PER FBC PL 606.1(5) |