| 2017-01-09 08:35:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.0.02 - THE IS AN INCORRECT REFERENCE TO |
| | THE FIRE CODE; THE BROWARD COUNT ADMENDMENTS IS NOT |
| | APPLICABLE WITHIN THEI JURISDICTION. |
| | |
| | PLEASE REMOVE THE REFERENCE AND ENSURE NO CONFLICTS. |
| | |
| | |
| | |
| | 2) SHEET A 1.2.01 - THE LIFE SAFETY NOTES INDICATE |
| | REFERENCES TOA FIRE SPRINKLER AND FIRE ALARM. THESE |
| | NOTES ARE CONFUSING AS TO THEM BEING INSTALLED OR NOT. |
| | |
| | PLEASE CLARIFY AND REMOVE ANY REFERENCES IF NOT |
| | PROPOSED. |
| | |
| | |
| | |
| | 3) SHEET 1.2.01 & 2.1.02 - THERE ARE INDICATIONS OF AN |
| | EXIT, # 2, LEADING TO THE TERRACE; HOWEVER, THE TERRACE |
| | INDICATES RALINGS WITH NO EXIT VOID OR GATE. |
| | |
| | NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.7 DISCHARGE FROM EXITS. |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT |
| | DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH |
| | 7.7.1.4. |
| | |
| | PLEASE CLARIFY AND CORRECT. |
| | |
| | |
| | |
| | 4) SHEET 1.2.01 & 2.1.02 - THE ARE TWO EXITS INDICATED |
| | FROM THE ASSEMBLY ROOM WITH A SEPARATION OF 17.5 FT. |
| | THE EXITS ARE REQUIRED TO BE SEPARATED BY A MINIMUM OF |
| | HALF THE AREA DIMENSION. |
| | |
| | |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| | THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| | SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| | OTHER EMERGENCY CONDITION. |
| | |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| | DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| | LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| | LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| | ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED |
| | IN 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| | |
| | |
| | PLEASE REVIEW, CLARIFY AND/OR CORRECT. |
| | |
| | |
| | |
| | 5) SHEET A 2.1.02 - THERE ARE INDICATIONS OF LIGHT |
| | WIEGHT TRUSS DESIGN. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE A NOTE FOR THE APPLICABLE SIGNAGE AT THE |
| | FRONT ENTRANCE. |
| | |
| | |
| | |
| | 6) SHEET 6.2.01 - THERE IS A LABEL INDICATION WITHIN |
| | THE DOOR SCHEDULE OF A C45; HOWEVER, THERE IS NO |
| | CALL-OUT INDICATING/IDENTIFYING WHAT IT IS. |
| | |
| | PLEASE INDICATE WHAT C45 IS? |
| | |
| | |
| | |
| | 7) SHEET A 6.2.01 - IN THE DOOR SCHEDULE FOR DOOR 104, |
| | THAT SERVES ROOM 151, THERE IS NO EXIT DEVICE IN THE |
| | COMMENT SECTION. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 8) SHEET A 6.2.01 - THE IS A NOTE ON ALL THE EXIT DOORS |
| | OF A "CYLINDER KEY SYSTEM". PER NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. INDICATE IF THE DOORS |
| | WILL BE EQUIPPED WITH ANY LOCK/LATCH. IF THE DOORS WILL |
| | BE EQUIPPED WITH A LOCK/LATCH, INDICATE HOW THE |
| | LOCK/LATCH WILL BE RELEASED FROM THE EGRESS SIDE OF THE |
| | DOOR. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS |
| | AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY |
| | OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE LOCATED AS FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR OTHER THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN |
| | THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING |
| | OPERATION, UNLESS OTHERWISE SPECIFIED IN |
| | 7.2.1.5.10.3, 7.2.1.5.10.4, OR 7.2.1.5.10.6. |
| | |
| | |
| | FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | PLEASE ENSURE THAT EACH LOCKING DEVICE/SYSTEM COMPLIES |
| | WITH THE ABOVE REQUIREMENTS. |
| | |
| | |
| | |
| | 9) SHEET E 0.0.01 - THE LEGEND IS INDICATING FA |
| | DEVICES. THESE SYMBOLS/COMMENTS ARE CONFUSING AND ARE |
| | IN ADDITION TO # 2 ABOVE. |
| | |
| | IF THERE IS NO FIRE ALARM PROPOSED, NO REFENCES SHOULD |
| | BE INDICATED AND/OR REMOVED. |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |