| 2017-01-12 09:03:11 | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO ACCESS CONTROLS, |
| | CCTV, PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE |
| | WILL SUFFICE. |
| | 2. SHEET E1.1.0.1- PLEASE ADD A GENERAL NOTE TO SHEET |
| | TO INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| | SUFFICE |
| | 3. SHEET E1.1.0.1- ADD A NOTE TO MAINTAIN ALL |
| | ELECTRICAL EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION |
| | PER STATE AND CITY REGULATORY AGENCIES. |
| | 4. ADDRESS FIRE COMMENTS RELATED TO ELECTRICAL. |
| | 5. PLEASE PROVIDE AVAILABLE FAULT CURRENT AVAILABLE AT |
| | THE FPL SERVICE. ATTACH TO DOCUMENTS LETTER FROM |
| | FLORIDA POWER & LIGHT INDICATING AIC. SHOW AIC |
| | CALCULATION BASED ON INFORMATION PROVIDED BY UTILITY |
| | FOR APPROVAL. NEC 110.24 FBC 107 |
| | 6. SHOW AT THE SERVICE GROUNDING ELECTRODE CONDUCTOR A |
| | INTERSYSTEM BONDING TERMINAL PER NEC 250.94 |
| | 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 8. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| | AND COMPLETIONS DOCUMENTS. |
| | 9. PLEASE SHOW TO COMPLY WITH THE FBC ENERGY |
| | CONSERVATION THE MEANS FOR AUTOMATIC LIGHTING CONTROLS |
| | AND LIGHTING DENSITIES ALLOWANCES PER SECTION C405, |
| | C405.2. |
| | 10. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |