Plan Review Notes
Plan Review Notes For Permit 16120877
Permit Number 16120877
Review Stop Z
Sequence Number 3
Notes
Date Text
2017-05-05 15:17:34FAILED
  
 PROVIDE WRITTEN RESPONSE.
  
 1) REPEAT COMMENT: THANK YOU FOR PROVIDING THE CUT
 SHEET FOR THE FIRE DEPARTMENT ACCESS DRIVE LIGHT
 FIXTURES. YOU HAVE STATED THAT THE POLES WILL BE 10
 FEET IN HEIGHT, BUT NO CUT SHEETS WERE PROVIDED TO SHOW
 THE POLE AND THE GROUND FOUNDATION INSTALLATION.
  
 2) REVISED COMMENT: THE LANDSCAPE PLAN SHOWS FOUR
 LOCATIONS WHERE THE LIGHTS TO THE SOUTH AND EAST OF THE
 GARAGE (ADJACENT TO THE FIRE TRUCK ACCESS LANE) ARE
 PLACED CLOSE TO THE EXISTING TREES. THE LANDSCAPE PLAN
 SHOWS THE TREE CANOPY MAINTAINED ABOVE 14 FEET, SO THE
 CANOPY WILL NOT BE NEGATIVELY IMPACTED BY THE 10 FOOT
 POLES HEIGHT. HOWEVER, SINCE THE CUT SHEETS SHOWING HOW
 THE POLES ARE TO BE INSTALLED IN THE GROUND WERE NOT
 INCLUDED, STAFF CANNOT VERIFY HOW THE PROPOSED
 LOCATIONS IMPACT THE TREE ROOTS. PLEASE PROVIDE NOT
 ONLY THE FOUNDATION SIZE, BUT ALSO HOW BIG AN AREA IS
 REQUIRED TO INSTALL THE FOUNDATION. THIS AREA NEEDS TO
 BE A MINIMUM OF FIVE FEET AWAY FROM THE TREE TRUNK TO
 ENSURE THAT THE ROOT SYSTEM IS NOT DAMAGED.
  
 3) PLEASE PROVIDE FULL SIZED SHEETS EE001, EE200, EE201
 AND EE501 SINCE THE 11X17 ARE NOT READABLE.
  
 4) THE FINAL APPROVED LIGHTING PLAN WILL NEED TO BE
 INCLUDED WITH THE AS BUILT MINOR PD AMENDMENT PRIOR TO
 THE C.O. OF THE GARAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
2017-04-11 16:05:16ROUTED TO ERIC SCHNEIDER