| Plan Review Notes For Permit 16120877 |
| Permit Number |
16120877 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-03 13:37:35 | FAILED | | | | | | 1) THERE WAS NO CUT SHEET INCLUDED LABELED "FIRE" TO | | | SHOW THE DSX0 LED 20C 530 40K T2M TYPE LIGHTS. | | | | | | A. HOW TALL ARE THESE POLES WITH FIXTURES? | | | B. THE PHOTOMETRIC PLANS SHALL INCLUDE THESE LIGHTS. | | | | | | 2) THE LANDSCAPE PLAN SHOWS NUMEROUS CONFLICTS WHERE | | | THE LIGHTS TO THE SOUTH AND EAST OF THE GARAGE | | | (ADJACENT TO THE FIRE TRUCK ACCESS LANE) ARE PLACED TOO | | | CLOSE TO THE EXISTING TREES. THE LIGHT POLES MUST BE | | | CENTERED BETWEEN THE TREES, AT LEAST 4 FEET FROM THE | | | PALM TREES AND 10 FEET FROM THE OAK OR MAHOGANY (SHADE) | | | TREES. | | | | | | 3) THE RESUBMITTAL PACKAGE ONLY HAS ONE COPY OF SHEETS | | | EE001, EE200, EE201 AND EE501. PLEASE SUBMIT ADDITIONAL | | | PLANS SO THAT THERE ARE THREE COMPLETE PERMIT SETS. | | | | | | 4) THE FINAL APPROVED LIGHTING PLAN WILL NEED TO BE | | | INCLUDED WITH THE AS BUILT MINOR PD AMENDMENT PRIOR TO | | | THE C.O. OF THE GARAGE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | 2017-02-24 11:32:48 | ROUTED TO ERIC SCHNEIDER |
|