Plan Review Notes
Plan Review Notes For Permit 16120877
Permit Number 16120877
Review Stop Z
Sequence Number 2
Notes
Date Text
2017-03-03 13:37:35FAILED
  
 1) THERE WAS NO CUT SHEET INCLUDED LABELED "FIRE" TO
 SHOW THE DSX0 LED 20C 530 40K T2M TYPE LIGHTS.
  
 A. HOW TALL ARE THESE POLES WITH FIXTURES?
 B. THE PHOTOMETRIC PLANS SHALL INCLUDE THESE LIGHTS.
  
 2) THE LANDSCAPE PLAN SHOWS NUMEROUS CONFLICTS WHERE
 THE LIGHTS TO THE SOUTH AND EAST OF THE GARAGE
 (ADJACENT TO THE FIRE TRUCK ACCESS LANE) ARE PLACED TOO
 CLOSE TO THE EXISTING TREES. THE LIGHT POLES MUST BE
 CENTERED BETWEEN THE TREES, AT LEAST 4 FEET FROM THE
 PALM TREES AND 10 FEET FROM THE OAK OR MAHOGANY (SHADE)
 TREES.
  
 3) THE RESUBMITTAL PACKAGE ONLY HAS ONE COPY OF SHEETS
 EE001, EE200, EE201 AND EE501. PLEASE SUBMIT ADDITIONAL
 PLANS SO THAT THERE ARE THREE COMPLETE PERMIT SETS.
  
 4) THE FINAL APPROVED LIGHTING PLAN WILL NEED TO BE
 INCLUDED WITH THE AS BUILT MINOR PD AMENDMENT PRIOR TO
 THE C.O. OF THE GARAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
2017-02-24 11:32:48ROUTED TO ERIC SCHNEIDER