Plan Review Notes
Plan Review Notes For Permit 16120877
Permit Number 16120877
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-23 14:17:50BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMITTAL BY THOMS J. ROGERS, P.E. OF ONM&J, INC.
 SPECIFIES A TYPE SF22 LIGHTING POLE (POLE CAT. NO.
 RSS-10-40-1, MODIFIED) FOR FIXTURE HEIGHT OF 22' - 0",
 POLE HEIGHT NOT SHOWN.
 WIND LOAD DESIGN OF HAPCO ROUND TAPERED ALUMINUM
 LIGHTING POLES (HAPCO CAT. NO. RS- 10B4-4) PREPARED BY
 DENNIS M. PATRICK, P.E. SPECIFIES FIXTURE HEIGHT OF
 9'-6" AND POLE HEIGHT OF 10'-00".
 PERMIT SET OF PLANS PREPARED BY M.F. GARCIA, P.E.
 SPECIFIES THE FOLLOWING PROPOSED POLE/FIXTURE HEIGHTS:
 16'-4" AND 10'-00" (PLAN PG. EE001)
 30'-00" (PLAN PG. EE501)
 FIXTURE MOUNTED ON POLE 17'-00" ABOVE GRADE (PLAN PG.
 EE201)
 22'-00" (PHILIP LUMEC SPEC. SHEET)
  
 PROVIDE DESIGN WIND LOAD SCHEDULE FOR EACH TYPE OF
 FIXTURE HEIGHT/ POLE HEIGHT COMBINATION.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 2. PROVIDE FOUNDATION SCHEDULE FOR EACH TYPE OF POLE
 INSTALLED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  