| Plan Review Notes For Permit 16120868 |
| Permit Number |
16120868 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-30 12:20:41 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- WINDOW CORNER DETAIL IS INCORRECT. PER MEETING WITH | | | CONTRACTOR, THE CORNER IS CONCRETE BLOCK CONSTRUCTION | | | NOT WOOD FRAMED CONSTRUCTION. REVISE AS REQUIRED TO | | | MATCH ACTUAL CONDITIONS. SEC. R301.1 FBC-RESIDENTIAL, | | | 5TH EDITION (2014). | | | | | | 2- STRUCTURAL CORNER DETAIL IS NOT CLEAR. A) WHAT ARE | | | THE #6 TEK SCREW ATTACHING TO THE 3" STEEL COLUMN?. | | | WHAT IS THE SIMPSON SPH4Z HOLDING? ENGINEER TO PROVIDE | | | CALCULATIONS SHOWING HOW THE STRUCTURAL BUCK DETAIL IS | | | TRANSFERRING THE LOADS TO THE 3" STEEL COLUMN? SEC. | | | 107.2.1.3 CITY AMENDMENTS. | | | | | | 3- WINDOW SCHEDULE IS NOT CLEAR. CONTRACTOR SAYS THAT | | | THERE ARE ONLY CASEMENT WINDOWS. THERE ARE NOT FIXED | | | AND SINGLE HUNG WINDOWS. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR CASEMENT | | | WINDOWS AS REQUIRED BY FAC61G20-3.002(33). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (5610805-6712 | | | [email protected] |
|