2017-01-20 13:23:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) A "NO PRESSURE TEST" NOTE IS INDICATED ON THE
 SUBMITTAL.
  
 PER NFPA 13, A "NO PRESSURE TEST" IS NOT INDICATED IN
 ANY CODE REFERENCE.
  
 PER NFPA 13, WHERE A SYSTEM CAN NOT BE ISOLATED A
 "SYSTEM WORKING PRESSURE TEST" SHALL BE DONE.
  
  
 SPRINKLER TESTING
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
  
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE OR VISUAL LEAKAGE.
  
  
 PLEASE ENSURE A PRESSURE GAUGE IS PROVIDED AND THE
 SYSTEM WORKING PRESSURE IS IDENTIFIED. A TEST WILL
 CONDUCTED FOR 2 HOURS DOCUMENTING ANY PRESSURE LOSS OR
 VISUAL LEAKAGE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  