| 2017-01-20 13:23:22 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 1) A "NO PRESSURE TEST" NOTE IS INDICATED ON THE |
| | SUBMITTAL. |
| | |
| | PER NFPA 13, A "NO PRESSURE TEST" IS NOT INDICATED IN |
| | ANY CODE REFERENCE. |
| | |
| | PER NFPA 13, WHERE A SYSTEM CAN NOT BE ISOLATED A |
| | "SYSTEM WORKING PRESSURE TEST" SHALL BE DONE. |
| | |
| | |
| | SPRINKLER TESTING |
| | 24.2 ACCEPTANCE REQUIREMENTS. |
| | 24.2.1* HYDROSTATIC TESTS. |
| | 24.2.1.1 UNLESS PERMITTED BY 24.2.1.2 THROUGH 24.2.1.8, |
| | ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO |
| | SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED |
| | AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE |
| | WITHOUT LOSS FOR 2 HOURS. |
| | |
| | 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS |
| | RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF |
| | SYSTEM WORKING PRESSURE. |
| | |
| | 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE |
| | PRESSURE OR VISUAL LEAKAGE. |
| | |
| | |
| | PLEASE ENSURE A PRESSURE GAUGE IS PROVIDED AND THE |
| | SYSTEM WORKING PRESSURE IS IDENTIFIED. A TEST WILL |
| | CONDUCTED FOR 2 HOURS DOCUMENTING ANY PRESSURE LOSS OR |
| | VISUAL LEAKAGE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |