| 2016-12-28 16:45:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE IS A CALL-OUT NOTE - 01 - INDICATING |
| | PRELIMIARY FIRE PROTECTION PLAN AND IN PARENTHESES "FOR |
| | REFERENCE ONLY - COMPLETE ENGINEERED FIRE PROTECTION |
| | SHOP DRAWING PLANS TO BE PROVIDED FOR REVIEW AND |
| | APPROVAL" |
| | |
| | PLEASE CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | 2) PLEASE PROVIDE MANUFACTURES SPEC SHEETS FOR ALL |
| | INSTALLED EQUIPMENT FOR FEILD VERIFICATION PURPOSES. |
| | |
| | |
| | |
| | 3) PER NFPA 13 THERE ARE MORE THAN 20 HEADS AND THE |
| | MODIFICATIONS SUCH AS RELOCATED DROPS THAT CAN NOT BE |
| | ISOLATED SHALL NOT REQUIRE TESTING IN EXCESS OF WORKING |
| | PRESSURE. |
| | |
| | AN ISOLATION VALVE CAN NOT BE INSTALLED ON AN ARM OVER, |
| | BUT IT CAN BE INSTALLED FOR THE ENTIRE SYSTEM IF |
| | POSSIBLE AND APPLICABLE. |
| | |
| | THE INSTALLTION IS LIMITED TO AN OCCUPANCY THAT MAY |
| | HAVE AN ISOLATION VALVE OR ONE THAT CAN BE INSTALLED |
| | FOR TESTING OF 200PSI FOR 2 HOURS. |
| | |
| | PLEASE REVIEW THIS INSTALLATION AND PROVIDE AN |
| | ISOLATION VALVE IF POSSIBLE AND APPLICABLE. |
| | |
| | PROVIDE A NOTE INDICATING IF ONE WILL BE INSTALLED OR |
| | WHY IT CAN NOT BE INSTALLED. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |