Plan Review Notes
Plan Review Notes For Permit 16120833
Permit Number 16120833
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-28 16:45:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS A CALL-OUT NOTE - 01 - INDICATING
 PRELIMIARY FIRE PROTECTION PLAN AND IN PARENTHESES "FOR
 REFERENCE ONLY - COMPLETE ENGINEERED FIRE PROTECTION
 SHOP DRAWING PLANS TO BE PROVIDED FOR REVIEW AND
 APPROVAL"
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 2) PLEASE PROVIDE MANUFACTURES SPEC SHEETS FOR ALL
 INSTALLED EQUIPMENT FOR FEILD VERIFICATION PURPOSES.
  
  
  
 3) PER NFPA 13 THERE ARE MORE THAN 20 HEADS AND THE
 MODIFICATIONS SUCH AS RELOCATED DROPS THAT CAN NOT BE
 ISOLATED SHALL NOT REQUIRE TESTING IN EXCESS OF WORKING
 PRESSURE.
  
 AN ISOLATION VALVE CAN NOT BE INSTALLED ON AN ARM OVER,
 BUT IT CAN BE INSTALLED FOR THE ENTIRE SYSTEM IF
 POSSIBLE AND APPLICABLE.
  
 THE INSTALLTION IS LIMITED TO AN OCCUPANCY THAT MAY
 HAVE AN ISOLATION VALVE OR ONE THAT CAN BE INSTALLED
 FOR TESTING OF 200PSI FOR 2 HOURS.
  
 PLEASE REVIEW THIS INSTALLATION AND PROVIDE AN
 ISOLATION VALVE IF POSSIBLE AND APPLICABLE.
  
 PROVIDE A NOTE INDICATING IF ONE WILL BE INSTALLED OR
 WHY IT CAN NOT BE INSTALLED.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  