| Plan Review Notes For Permit 16120787 |
| Permit Number |
16120787 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-02-27 12:26:25 | 1) SHT. L2.10 - DETAIL #5 - THESE DRINKING FOUNTAINS | | | SHALL COMPLY WITH 2014 FBC -ACCESSIBILITY SEC.211.1. | | | WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING | | | FOUNTAINS SPECIFIED IN SEC.211.2 ARE PROVIDED, 50 | | | PERCENT OF THE TOTAL NUMBER OF DRINKING FOUNTAINS | | | PROVIDED SHALL COMPLY WITH FAC SEC.602.1 THROUGH 602.6 | | | AND 50 PERCENT OF THE TOTAL NUMBER OF DRINKING | | | FOUNTAINS PROVIDED SHALL COMPLY WITH SEC. 602.7. PER | | | THE MANUFACTURER'S WEBSITE, THE MODEL OF THE DRINKING | | | FOUNTAIN SPECIFIED IN DETAIL #5 DOES NOT COMPLY WITH | | | THE PREVIOUS REFERENCED CODE SECTIONS. | | | 2) SHT. L2.10 - DETAIL #9 - THE SPECIFIED SHOWER SHALL | | | COMPLY WITH 2014 FBC-ACCESSIBILITY SEC.213.3.6. PER THE | | | MANUFACTURER'S WEBSITE, THE MODEL OF THE SHOWER | | | SPECIFIED IN DETAIL #9 DOES NOT COMPLY WITH THE FAC. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|