| Plan Review Notes For Permit 16120787 |
| Permit Number |
16120787 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-24 07:27:46 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120787 | | | 1/24/17 | | | | | | 1) REFER TO SECTION 404.2 AND PROVIDE CODE COMPLIANT | | | NATURAL VENTILATION CALCULATIONS FOR THE STORAGE ROOM, | | | THE MEN/WOMEN'S RESTROOMS, AND THE SERVICE/PUMP ROOM. | | | | | | 2) REFER TO SECTION 309.1 AND PROVIDE A SPACE HEATING | | | SYSTEM FOR THE MAINTENANCE/STORAGE ROOM. PLEASE INCLUDE | | | SYSTEM SIZING CALULATIONS PER SECTION C403.2.1 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 3) PROVIDE DOCUMENTATION OF ENERGY CONSERVATION | | | COMPLIANCE PER SECTION C101.2 AND C401.2. | | | | | | 4) PROVIDE DETAILS FOR ATTACHMENT OF THE FANS AND FAN | | | CURBS TO THE ROOF STRUCTURE- SECTION 301.15. | | | | | | 5) SUBMIT A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA | | | FOR THE WALL LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|