| 2017-01-18 16:37:31 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16120787 RESTROOM PAVILION |
| | ADD: 5100 N. HAVERHILL RD. |
| | CONT: STRATICON LLC |
| | TEL: 772-210-0700 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 18/2016 |
| | ACTION: DENIED |
| | |
| | 1) THERE ARE 2 PAVILIONS AND ONE BUILDING WITH |
| | RESTROOMS UNDER THE SAME ADDRESS. EACH BUILDING NEEDS |
| | IT OWN ADDRESS FOR IDENTIFICATION DURING CONSTRUCTION |
| | AS WELL AS FOR POLICE AND FIRE RESPONSE. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION OF THE PROJECT. |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040 |
| | E-MAIL: [email protected] |
| | |
| | 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 8. STRUCTURAL REQUIREMENTS COLUMNS, BEAMS AN ROOF |
| | FRAMING MEMBERS, COMPONENTS AND CLADDING. |
| | |
| | 3) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) DOORS |
| | (C) WALL LOUVERS |
| | (D) ROOFING ASSEMBLIES. 1 1/2 METAL DECKING AND |
| | STANDING SEAM METAL ROOF, SELF ADHERING UNDERLAYMENT |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | |
| | 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) SHEET A-3.01 BUILDING SECTION. THE SECTION PLAN |
| | INDICATES FLOAT FINISH PLASTER CEILINGS. THE QUESTION |
| | IS ARE THE CEILINGS AND WALLS TO BE ACTUAL PLASTER OR |
| | ARE THEY GOING TO BE CEMENT PLASTER (STUCCO)? IF THE |
| | CEILINGS ARRE TO BE CEMENT PLASTER (STUCCO) THEN SHOW |
| | COMPLIANCE WITH 2014 FBC-B 2510.1 EXTERIOR AND INTERIOR |
| | CEMENT PLASTER AND LATHING SHALL BE DONE WITH THE |
| | APPROPRIATE MATERIALS LISTED IN TABLE 2507.2 AND |
| | CHAPTER 35. 2510.3 INSTALLATION. INSTALLATION OF THESE |
| | MATERIALS SHALL BE IN COMPLIANCE WITH ASTM C 926 AND |
| | ASTM C 1063. PLEASE PROVIDE THE TYPE OF WIRE LATH, |
| | WEIGHT OF THE METAL PLASTER BASE AND THE MAXIUM |
| | PERMISSIBLE SPACING OF SUPPORTS ASSTM C1063. |
| | |
| | 6) SHEET A-4.01 THE RESTROOM INTERIOR ELEVATIONS. |
| | PLEASE REVIEW THE WATER CLOSET GRAB BARS SHOW 36 INCHES |
| | CENTERLINED. PLEASE BE AWARE UNDER THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BAR THE VERTICAL DIMENSION IS TAKEN FROM THE FLOOR TO |
| | THE TOP OF THE GRASPABLE SURFACE. |
| | |
| | 7) MISSING SOILS REPORT, NOT SUBMITTED IN THIS REVIEW. |
| | 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |