Plan Review Notes
Plan Review Notes For Permit 16120779
Permit Number 16120779
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-12 17:09:051ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE FLOOR PLAN SHOWING ALL PLUMBING FIXTURES
 INCLUDING SINK THAT THE GREASE INTERCEPTOR IS BEING
 CONNECTED TO. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE WATER AND SANITARY RISER DIAGRAM . PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 3. PROVIDE MANUFACTURE SPEC FOR GREASE INTERCEPTOR. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SIZING CALCULATIONS AND PLAN MUST BE DESIGNED BY A
 DESIGN PROFESSIONAL OR PLUMBING CONTRACTOR THE SIZING
 CALCULATION COULD BE DONE BY MANUFACTURE. PER WPB AMEND
 TO FBC 107.3.4.3
  
 5. COMPLY WITH BUILDING AND FIRE COMMENTS. PER WPB
 AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  