| Plan Review Notes For Permit 16120779 |
| Permit Number |
16120779 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-12 17:09:05 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE FLOOR PLAN SHOWING ALL PLUMBING FIXTURES | | | INCLUDING SINK THAT THE GREASE INTERCEPTOR IS BEING | | | CONNECTED TO. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PROVIDE WATER AND SANITARY RISER DIAGRAM . PER WPB | | | AMEND TO FBC 107.3.5.1.3(13) | | | | | | 3. PROVIDE MANUFACTURE SPEC FOR GREASE INTERCEPTOR. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 4. SIZING CALCULATIONS AND PLAN MUST BE DESIGNED BY A | | | DESIGN PROFESSIONAL OR PLUMBING CONTRACTOR THE SIZING | | | CALCULATION COULD BE DONE BY MANUFACTURE. PER WPB AMEND | | | TO FBC 107.3.4.3 | | | | | | 5. COMPLY WITH BUILDING AND FIRE COMMENTS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|