| 2017-01-03 12:15:56 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PLEASE PROVIDE A ONE-LINE DIAGRAM REFLECTING ALL |
| | PANELBOARDS, CONDUIT AND CONDUCTOR SIZE ARRANGEMENT. |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA. |
| | 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL ELECTRICAL |
| | LOADS; EXAMPLE LIGHTING, RECEPTACLES AND MECHANICAL |
| | EQUIPMENT. LOAD CALCULATIONS REQUIRED TO BE WITHIN |
| | GENERATOR CAPACITY. FBC 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA. |
| | 3. SHOW BONDING AND GROUNDING SCHEME FOR THE GENERATOR |
| | AND ANY CONDUCTIVE METAL PARTS OF THE TENT. FOLLOW NEC |
| | 250 REQUIREMENTS. |
| | 4. PROVIDE A FIXTURE SCHEDULE AND PRODUCT DATA SHEETS |
| | REFLECTING ALL LIGHTING FIXTURES BEING USED. LISTINGS |
| | WILL BE VERIFIED. FBC 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA. |
| | 5. PROVIDE GENERAL NOTES TO COMPLY WITH ALL APPLICABLE |
| | TEMPORARY REQUIREMENTS PER NEC 590, REGARDING GFCI |
| | PROTECTION, PROTECTION AGAINST ACCIDENTAL DAMAGE |
| | (CORDS), LAMP PROTECTION, SUPPORTS ETC. |
| | 6. EXITS SIGNS AND EM LIGHTING ADDRESSED UNDER FIRE |
| | REVIEW COMMENTS. |
| | 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |