| Plan Review Notes For Permit 16120745 |
| Permit Number |
16120745 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-03 10:55:05 | PROVISO | | | | | | TAP CONDUCTORS SHOWN FROM METAL WIREWAY TO BOTH ATS TO | | | BE WITHIN NEC 240.21B REQUIREMENTS. | | | | | | PROVIDE SINAGE PER NEC 700.7 | | | |
|