| 2016-12-22 08:10:43 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION PERMIT #16120736 | | | MASTER # 16041276 | | | 12/22/16 | | | | | | 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETUIRN AIR | | | SYSTEMS OF RTU'S 1-3 UNLESS MANUFACTURER'S | | | SPECIFICATIONS SHOW THE UNITS CANNOT PRODUCE OVER 2000 | | | CFMS. PLEASE SHOW THE DETECTOR LOCATIONS AS REQUIRED BY | | | 606.2.1, AND INDICATE HOW THEY WILL BE SUPOERVISED PER | | | SECTION 606.4.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|