2016-12-22 08:10:431ST REVIEW FBC-2014 MECHANICAL
 REVISION PERMIT #16120736
 MASTER # 16041276
 12/22/16
  
 1) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETUIRN AIR
 SYSTEMS OF RTU'S 1-3 UNLESS MANUFACTURER'S
 SPECIFICATIONS SHOW THE UNITS CANNOT PRODUCE OVER 2000
 CFMS. PLEASE SHOW THE DETECTOR LOCATIONS AS REQUIRED BY
 606.2.1, AND INDICATE HOW THEY WILL BE SUPOERVISED PER
 SECTION 606.4.1.
  