| Plan Review Notes For Permit 16120735 |
| Permit Number |
16120735 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-21 14:32:38 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE CURRENT REVISED FLORIDA PRODUCT APPROVAL FOR | | | ROOF TILES AND ROOF TILE UNDERLAYMENT SUBMITTED. FAC | | | 61G20-3.002(33). | | | | | | 2- SPECIFY ROOF TILE FASTENING METHOD TO VERIFY DESIGN | | | PRESSURES. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION | | | (2014) | | | | | | 3- FLAT ROOF NOA 12-1003.05 SUBMITTED: | | | A) SPECIFY ASSEMBLY TO BE INSTALLED. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS. SEC. | | | R301.1 FBC-RESIDENTIAL. | | | | | | 4- VALUATION LOW. PROVIDE COPY OF SIGNED CONTRACT. SEC. | | | 109.3 CITY AMENDMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|