| 2017-01-24 10:30:14 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE OWNER'S NAME ON THE ENERGY FORM R405-2014, DIEGO |
| | BREITFELD, DOES NOT MATCH THE PERMIT APPLICATION, OWNER |
| | BUILDER AFFIDAVIT OR THE PROPERTY APPRAISER. OUR |
| | RECORDS SHOW ELIZABETH VICAINO IS THE OWNER. PLEASE |
| | CORRECT. |
| | |
| | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | FORMS. FBC ENERGY CONSERVATION SECTION R103.1.1.2 |
| | |
| | 3) PROVIDE TWO SETS OF CONDENSER ANCHORING |
| | DETAILS.FBCR-M1307.2 ANCHORAGE OF APPLIANCES. |
| | APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE |
| | FASTENED OR ANCHORED IN AN APPROVED MANNER. |
| | |
| | 4) THE EQUIPMENT SIZING CALCULATIONS HAVE A REQUIRED |
| | TOTAL COOLING OF 23,017 BTUS OR 1.92 TONS. THE ACTUAL |
| | LISTED IS FOR 27,600 BTUS OR 2.3 TONS. THE PLANS |
| | SPECIFY A 2.5 TON UNIT WITH 27,600 BTUS. BASED ON THE |
| | SIZING CALCULATIONS A 2 TON UNIT WITH 24,000 BTUS |
| | SHOULD BE USED. FBC ENERGY CONSERVATION SECTION |
| | R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY |
| | EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY |
| | IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT |
| | MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD |
| | CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN |
| | SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED |
| | BY THE MANUFACTURER'S PRODUCT LINES. THE CORRESPONDING |
| | LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN |
| | THE CALCULATED LATENT LOAD. |
| | |
| | |