2017-01-24 10:30:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER'S NAME ON THE ENERGY FORM R405-2014, DIEGO
 BREITFELD, DOES NOT MATCH THE PERMIT APPLICATION, OWNER
 BUILDER AFFIDAVIT OR THE PROPERTY APPRAISER. OUR
 RECORDS SHOW ELIZABETH VICAINO IS THE OWNER. PLEASE
 CORRECT.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 FORMS. FBC ENERGY CONSERVATION SECTION R103.1.1.2
  
 3) PROVIDE TWO SETS OF CONDENSER ANCHORING
 DETAILS.FBCR-M1307.2 ANCHORAGE OF APPLIANCES.
 APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
 FASTENED OR ANCHORED IN AN APPROVED MANNER.
  
 4) THE EQUIPMENT SIZING CALCULATIONS HAVE A REQUIRED
 TOTAL COOLING OF 23,017 BTUS OR 1.92 TONS. THE ACTUAL
 LISTED IS FOR 27,600 BTUS OR 2.3 TONS. THE PLANS
 SPECIFY A 2.5 TON UNIT WITH 27,600 BTUS. BASED ON THE
 SIZING CALCULATIONS A 2 TON UNIT WITH 24,000 BTUS
 SHOULD BE USED. FBC ENERGY CONSERVATION SECTION
 R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY
 EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY
 IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT
 MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD
 CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN
 SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED
 BY THE MANUFACTURER'S PRODUCT LINES. THE CORRESPONDING
 LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN
 THE CALCULATED LATENT LOAD.
  
  