2017-03-28 16:30:38BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FOUNDATION REQUIRED PER ACI 318. MIN. 8" X 10" W/2
 #5 CONT.
 2. VERTICAL REINFORCEMENT PER TABLE 1807.2.4. 1 #4 AT
 EACH END/OPENING AND 72" O.C. KEEP REBAR TO SOIL SIDE
 OF BLOCK AND GROUT CELL.
 3. LOCATION - RETAINING WALL MAY BUTT UP TO BUT NOT
 ENCROACH EXISTING SIDEWALK. THIS APPLIES TO FOUNDATION
 AND CAP BLOCK.
 4. PLEASE SEE RED LINED PLANS FOR CLARIFICATION.