| Plan Review Notes For Permit 16120719 |
| Permit Number |
16120719 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-28 16:30:38 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. FOUNDATION REQUIRED PER ACI 318. MIN. 8" X 10" W/2 | | | #5 CONT. | | | 2. VERTICAL REINFORCEMENT PER TABLE 1807.2.4. 1 #4 AT | | | EACH END/OPENING AND 72" O.C. KEEP REBAR TO SOIL SIDE | | | OF BLOCK AND GROUT CELL. | | | 3. LOCATION - RETAINING WALL MAY BUTT UP TO BUT NOT | | | ENCROACH EXISTING SIDEWALK. THIS APPLIES TO FOUNDATION | | | AND CAP BLOCK. | | | 4. PLEASE SEE RED LINED PLANS FOR CLARIFICATION. |
|