| 2016-12-28 15:45:08 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | REVISION DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ONE SET OF THE REVISED PLANS IS MISSING SHEET A-1. |
| | TWO IDENTICAL SETS OF REVISED PLANS ARE REQUIRED TO BE |
| | SUBMITTED. FBC 107.1 |
| | |
| | 2) ONE SET OF REVISED PLANS HAS TWO DIFFERENT A-3 |
| | SHEETS THAT BOTH HAVE THE SAME REVISION DATE. PLEASE |
| | REMOVE THE ONE THAT DOES NOT CONTAIN THE CORRECT |
| | INFORMATION. FBC 107.2.1 |
| | |
| | 3) ON SHEET A-1.1 THE WINDOW ID TAGS FOR THE REVISED |
| | WINDOWS ARE STILL SHOWN AS D. THESE ARE NOW SINGLE |
| | WINDOWS AND ARE NOT 60" WIDE SLIDER TYPE. FBC 107.2.1 |
| | |
| | 4) THE DESIGN PRESSURES FOR THE ROOF IN THE TABLE ON |
| | SHEET S-2 ARE INCORRECT. THE PRESSURES ARE LOW AND DO |
| | NOT CORRESPOND WITH THE CORRECT PRESSURES THAT LISTED |
| | ON SHEET S-1. FBC-R 301.2.1 |
| | |
| | 5) THE REVISED PLANS SHOW A DOOR THAT OPENS FROM THE |
| | GARAGE INTO THE GUEST BEDROOM WHICH IS NOT ALLOWED BY |
| | CODE. FBC-R302.5.1 OPENING PROTECTION. |
| | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM |
| | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. |
| | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL |
| | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8 |
| | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB-CORE |
| | STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR |
| | 20-MINUTE FIRE-RATED DOORS, EQUIPPED WITH A |
| | SELF-CLOSING DEVICE. |
| | |
| | |
| | |