| Plan Review Notes For Permit 16120673 |
| Permit Number |
16120673 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-04 13:42:39 | 2ND REVIEW FBC-2014 BUILDING | | | PERMIT #16120673 | | | 1/4/17 | | | | | | 1) SEE LIMITATION #7 ON PAGE 30 OF THE NOA #14-1030.02, | | | AND SUBMIT ENGINEERED CALCULATIONS FOR ENHANCED | | | FASTENER DENSITIES IN THE PERIMETER AND CORNER AREAS OF | | | THE ROOF. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|