Plan Review Notes
Plan Review Notes For Permit 16120624
Permit Number 16120624
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-22 15:01:341ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] IN ADDITION TO THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN, THE APPLICABLE CODES &
 SCOPE OF WORK SHALL BE NOTED ON THE PLANS. FBC-107
  
 2] THE STATED VALUATION OF $3,200 IS TOO LOW FOR THE
 PROPOSED WORK. THE PERMIT VALUATION AND PERMIT FEE MUST
 BE COMMENSURATE WITH THE VALUATION AND FEE THAT A
 LICENSED CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE
 VALUATION ACCORDINGLY (SHOW AN OWNER SIGNED CONTRACT).
 FBC-109
  
 3] ADD GENERAL ELECTRICAL NOTES FOR AFCI PROTECTION &
 TAMPER RESISTANT RECEPTACLES PER FBC-R SECTIONS
 E3902.13, E4002.14.
  
 4] SMOKE ALARMS REQUIRED PER SECTION FBC 314 & 315.
 IDENTIFY CARBON MONOXIODE COMBO ALARMS WITHIN 10'
 OUTSIDE OF THE BEDROOMS.
  
 5] CLARIFY IF SUB PANEL IS LOCATED IN BATHROOM ? FBC-R
 SECTION E3705.7.
  
 6] ADD AN INTERSYSYTEM BONDING TERMINAL AT THE SERVICE
 PER FBC-R SECTION E3609.3.