| Plan Review Notes For Permit 16120622 |
| Permit Number |
16120622 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-21 10:52:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PACKET DOES NOT INCLUDE VOLTAGE DROP, | | | BATTERY CALCULATIONS AND WIRING DIAGRAM FOR ALL | | | DEVICES. | | | | | | PLEASE PROVIDE THE ABOVE PER NFPA 101 CHAPTER 9, | | | BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT | | | | | | 9.6.1.3 A FIRE ALARM SYSTEM REQUIRED FOR LIFE SAFETY | | | SHALL BE INSTALLED, TESTED, AND MAINTAINED IN | | | ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF NFPA 70, | | | NATIONAL ELECTRICAL CODE, AND NFPA 72, NATIONAL FIRE | | | ALARM AND SIGNALING CODE, UNLESS IT IS AN APPROVED | | | EXISTING INSTALLATION, WHICH SHALL BE PERMITTED TO BE | | | CONTINUED IN USE. | | | | | | | | | PLEASE PROVIDE THE ABOVE REQUIRED DOCUMENTATION. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|