Plan Review Notes
Plan Review Notes For Permit 16120583
Permit Number 16120583
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-13 16:02:191ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A-02 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. SHT. A-02 FLUSH CONTROLS SHALL BE LOCATED ON THE
 OPEN SIDE OF THE WATER CLOSET. FBC ACC 604.6
  
 3, SHT. A-02 THE OUTLET OF THE TOILET PAPER DISPENSER
 SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 INCHES (1220
 MM) MAXIMUM ABOVE THE FINISH FLOOR . FBC ACC 604.7
  
  
  