| Plan Review Notes For Permit 16120583 |
| Permit Number |
16120583 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-28 09:41:46 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120583 | | | 12/28/16 | | | | | | 1) SHEET A-01 & M-1: PLEASE ADJUST THE EXHAUST | | | CALCULATION FOR THE LOCKER ROOM BASED ON THE FLOOR PLAN | | | DIMENSIONS. SHOW THE LOCATION OF EF-3 AND CLARIFY WHICH | | | AREAS IT IS SERVING AND IT'S CFM CAPACITY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|