| 2016-12-22 12:21:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 01 - THERE IS AN INDICATION THAT THE |
| | BUILDING IS FULLY SPRINKLERED. THERE IS NO INDICATION |
| | OF FIRE SPRINKLER OR FIRE ALARM WORK BEING UNDER |
| | SEPARATE PERMIT AND SHOP DRAWING BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE WITH THE ABOVE |
| | REQUIREMENT. |
| | |
| | |
| | |
| | 2) SHEET A 03 & E 2 - THERE IS INDICATION OF A CARD |
| | READER SYSTEM. THE CARD READER SYSTEM SHALL BE UNDER |
| | SEPARATE PERMIT AND NOT APPROVED WITH THIS PERMIT. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 04 - A NEW LADDER TO SERVICE THE CATWALK IS |
| | INDICATED. THIS LADDER IS A FIRE ESCAPE LADDER FOR |
| | THOSE USING THE CAT WALK. THIS LADDER SHALL COMPLY WITH |
| | THE REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF |
| | EGRESS. |
| | |
| | |
| | 7.2.9 FIRE ESCAPE LADDERS. |
| | 7.2.9.1 GENERAL. FIRE ESCAPE LADDERS COMPLYING WITH |
| | 7.2.9.2 AND |
| | 7.2.9.3 SHALL BE PERMITTED IN THE MEANS OF EGRESS ONLY |
| | WHERE PROVIDING ONE OF THE FOLLOWING: |
| | (1) ACCESS TO UNOCCUPIED ROOF SPACES AS PERMITTED IN |
| | 7.2.8.3.4 |
| | (2) SECOND MEANS OF EGRESS FROM STORAGE ELEVATORS AS |
| | PERMITTED IN CHAPTER 42 |
| | (3) MEANS OF EGRESS FROM TOWERS AND ELEVATED PLATFORMS |
| | AROUND MACHINERY OR SIMILAR SPACES SUBJECT TO OCCUPANCY |
| | NOT TO EXCEED THREE PERSONS WHO ARE ALL CAPABLE OF |
| | USING THE LADDER |
| | (4) SECONDARY MEANS OF EGRESS FROM BOILER ROOMS OR |
| | SIMILAR SPACES SUBJECT TO OCCUPANCY NOT TO EXCEED THREE |
| | PERSONS WHO ARE ALL CAPABLE OF USING THE LADDER |
| | (5) ACCESS TO THE FINISHED GROUND LEVEL FROM THE LOWEST |
| | BALCONY OR LANDING OF A FIRE ESCAPE STAIR FOR SMALL |
| | BUILDINGS AS PERMITTED IN 7.2.8.4 WHERE APPROVED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | 7.2.9.2 CONSTRUCTION AND INSTALLATION. |
| | 7.2.9.2.1 FIRE ESCAPE LADDERS SHALL COMPLY WITH ANSI |
| | A14.3, SAFETY REQUIREMENTS FOR FIXED LADDERS, UNLESS |
| | ONE OF THE FOLLOWING CRITERIA IS MET: |
| | (1) APPROVED EXISTING LADDERS COMPLYING WITH THE |
| | EDITION OF THIS CODE THAT WAS IN EFFECT WHEN THE |
| | LADDERS WERE INSTALLED SHALL BE PERMITTED. |
| | (2) INDUSTRIAL STAIRS COMPLYING WITH THE MINIMUM |
| | REQUIREMENTS FOR FIXED STAIRS OF ANSI/ASSE A1264.1, |
| | SAFETY REQUIREMENTS FOR WORKPLACE FLOOR AND WALL |
| | OPENINGS, STAIRS AND RAILING SYSTEMS, SHALL BE |
| | PERMITTED WHERE FIRE ESCAPE LADDERS ARE PERMITTED IN |
| | ACCORDANCE WITH CHAPTER 40. |
| | 7.2.9.2.2 LADDERS SHALL BE INSTALLED WITH A PITCH THAT |
| | EXCEEDS 75 DEGREES. |
| | 7.2.9.3 ACCESS. THE LOWEST RUNG OF ANY LADDER SHALL NOT |
| | BE MORE THAN 12 IN. (305 MM) ABOVE THE LEVEL OF THE |
| | SURFACE BENEATH IT. |
| | |
| | PLEASE PROVIDE THE APPLICABLE DETAILED DRAWING |
| | INDICATING COMPLIANCE WITH THE ABOVE NOTED CODES |
| | |
| | |
| | |
| | 4) SHEET E 2 - PLEASE PROVIDE AN ADDITIONAL EXIT SIGN |
| | AT THE END OF THE NEW CORRIDOR AT THE OPEN SPACE |
| | LEADING TO THE EXISTING EXIT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |