Plan Review Notes
Plan Review Notes For Permit 16120583
Permit Number 16120583
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-22 15:28:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120583
 ADD: 6527 N. JOG RD.
 CONT: ONE CALL PROPERTY SERVICES, INC.
 TEL: 561-692-6277
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 22/ 2016
 ACTION: DENIED
  
 1) SHEET 01 SHOWS THE NEW WALLS OF THE PROPOSED LOCKER
 ROOM AS A PARTITION TYPE P1. PLEASE PROVIDE WHERE IN
 THE PLANS A P1 PARTITION IS FOUND. SHEET A-03 DETAIL #
 6 SHOWS THE SAME WALL AS A 1 HOUR PARTITION, A UL
 LISTING OF U419. UL LISTING U419 IS A 1 HOUR FIRE RATED
 NON-BEARING PARTITION. SHEET 03 DETAILS 6 & 7 BOTH SHOW
 A PLYWOOD UNDERLAYMENT AND SECONDARY SHEET OF ? INCH
 LEVLEROCK FLOOR UNDERLAYMENT.
  
 2) THE SHEET A03 DETAIL SHOWS A FLOOR / CEILING
 ASSEMBLY LISTED AS UL LISTING L524, PLEASE PROVIDE
 WHICH SYSTEM NUMBER THIS SERIES OF COMPONENTS IS? I
 DON?T FIND THESE COMPONENTS IN THE UL LISTING BOOK FOR
 A 1 HOUR FIRE RATING FLOOR/ CEILING ASSEMBLY. FBC-B
 TABLE 707.3.10.
  
 ? 3) SHEET A04 DETAIL # 6 SHOWS A NEW LADDER USED TO
 GAIN ACCESS TO THE EXISTING MECHANICAL PLATFORM AND
 EXISTING CATWALK. PLEASE SHOW COMPLIANCE WITH 2014
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ELEVATED
 STRUCTURES.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 3.1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 3.2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3.3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 3.4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 3.5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 3.6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 3.7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 4) SHEET A-02 SHOWS CERAMIC TILE ON THE RESTROOM WALLS
 BUT THERE IS NO MENTION OF THE TYPE OF BACKING TO BE
 INSTALLED. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 2509.2 BASE FOR TILE. GLASS MAT WATER-RESISTANT GYPSUM
 BACKING PANELS, DISCRETE NONASBESTOS FIBER-CEMENT
 INTERIOR SUBSTRATE SHEETS OR NONASBESTOS FIBER-MAT
 REINFORCED CEMENTITIOUS BACKER UNITS IN COMPLIANCE WITH
 ASTM C 1178, C 1288 OR C 1325 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS SHALL BE
 USED AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS
 AND WALL AND CEILING PANELS IN SHOWER AREAS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A
 BASE FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840 AND
 MANUFACTURER RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD
 IS PERMITTED UNDER TILE OR WALL PANELS IN OTHER WALL
 AND CEILING AREAS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840.
  
 5) SHEET A2 DETAILS A7, A8 & 08 ALL SHOW THE ACCESSIBLE
 WATER CLOSET GRAB BARS ARE SET AT 36 INCHES CENTERLINE
 OF THE GRAB BAR. PLEASE NOTE IN THE 2014
 FBC-ACCESSIBILITY CODE 609.4 THE GRAB BARS ARE MEASURED
 FROM FINISH FLOOR TO THE TOP OF THE GRASPING SURFACE,
 NOT CENTER LINED.
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  