Plan Review Notes
Plan Review Notes For Permit 16120571
Permit Number 16120571
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-17 04:59:291) INDICATE THE PSI OF THE SYSTEM ON BOTH DRAWINGS. FBC
 RES. SEC. G2413.2. .
 2) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
 3)SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 4) THE BRANCHES FOR THE GENERATOR, RANGE, FIREPLAC POOL
 HEATER AND GRILL ARE SHOWN ON THE RISER AS BEING ONLY
 ONE AND TWO FEET IN LENGTH WHICH DOESN'T MAKE SENSE AS
 THIS WOULD MEAN THEY ARE IN VERY CLOSE PROXIMITY OF
 EACH OTHER. THE TOTAL LENGTH OF EACH BRANCH MUST BE
 INCLUDED IN THE TOTAL DISTANCE FROM THE METER TO THE
 MOST REMOTE OUTLET AS THIS WILL INCREASE THE DISTANCE.
 SHOW THE CORRECT DISTANCE OF THE APPLIANCE FROM THE
 MAIN TO EACH OUTLET.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW