Plan Review Notes
Plan Review Notes For Permit 16120557
Permit Number 16120557
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-15 10:24:23RESIDENTIAL (R3) RE-ROOF REVISION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLAT ROOF PRODUCT APPROVAL FL1654-R19 SUBMITTED:
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH
 EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE
 "D". THE DESIGN PRESSURES FOR SELECTEDD W-138 ARE TOO
 LOW FOR THE PERIMETER AREAS. NEED TO SELECT AN ASSEMBLY
 THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF ZONES OR
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS TO
 ENHANCE THE NAIL FASTENING PATTERN TO INCREASE THE
 DESIGN PRESSURES.
  