| Plan Review Notes For Permit 16120544 |
| Permit Number |
16120544 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-15 16:25:44 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE MECHANICAL PLANS SHOWING CFM VALUES FOR ALL | | | SUPPLY OUTLETS IN ALL AREAS OF HOME (EXISTING AND NEW) | | | (2) CONFIRM AHU TOTAL DESIGN CFM QUANTITY MATCHES TOTAL | | | CFM FOR ALL SUPPLY OUTLETS IN ENTIRE HOME. | | | (3) BATHROOM EXHAUST IS 50 CFM MINIMUM ( SEE TABLE | | | M1507.4 BELOW) | | | | | | TABLE M1507.4 MINIMUM REQUIRED LOCAL EXHAUST RATES FOR | | | ONE- AND TWO-FAMILY DWELLINGS | | | | | | AREA TO BE EXHAUSTED EXHAUST RATES | | | KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTINUOUS | | | BATHROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACITY OF | | | 50 CFM | | | INTERMITTENT OR 20 CFM CONTINUOUS | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | (4) REVISE FORM R405-2014. PROVIDE CORRECT INFORMATION | | | FOR HVAC. | | | (5) REVISE HEAT LOAD CALCULATIONS SHOW ENTIRE HOME. | | | (6) PROVIDE AHRI | | | (7) PROVIDE CONDENSER TIE DOWN DETAIL | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|