Plan Review Notes
Plan Review Notes For Permit 16120544
Permit Number 16120544
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-15 16:25:44CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS SHOWING CFM VALUES FOR ALL
 SUPPLY OUTLETS IN ALL AREAS OF HOME (EXISTING AND NEW)
 (2) CONFIRM AHU TOTAL DESIGN CFM QUANTITY MATCHES TOTAL
 CFM FOR ALL SUPPLY OUTLETS IN ENTIRE HOME.
 (3) BATHROOM EXHAUST IS 50 CFM MINIMUM ( SEE TABLE
 M1507.4 BELOW)
  
 TABLE M1507.4 MINIMUM REQUIRED LOCAL EXHAUST RATES FOR
 ONE- AND TWO-FAMILY DWELLINGS
  
 AREA TO BE EXHAUSTED EXHAUST RATES
 KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTINUOUS
 BATHROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACITY OF
 50 CFM
 INTERMITTENT OR 20 CFM CONTINUOUS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (4) REVISE FORM R405-2014. PROVIDE CORRECT INFORMATION
 FOR HVAC.
 (5) REVISE HEAT LOAD CALCULATIONS SHOW ENTIRE HOME.
 (6) PROVIDE AHRI
 (7) PROVIDE CONDENSER TIE DOWN DETAIL
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  