| 2017-01-05 17:09:14 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16120521 |
| | W. P. B. PERMIT: 16050444 |
| | ADD: 3224 S. DIXIE HWY. |
| | CONT: ATLANTIC ENGINEERING SERVICES |
| | TEL: 561-358-4140 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 05/2017 |
| | ACTION: DENIED |
| | |
| | 1) BOTH SHEETS A2 AND LS1 ARE MISSING THE 2 HOUR RATING |
| | BETWEEN OCCUPANCIES SEE WALL BETWEEN THE OFFICE AND |
| | UNIT # 1. SEE 2014 FBC-B TABLE 508.4. |
| | |
| | 2) FROM THE 2ND PLAN REVIEW OF THE ISSUED PLAN SET OF |
| | DOCUMENTS, SEE FIRES PROVISO ON THE REAR STEPS |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STEPS. NOT |
| | INCORPORATED IN THIS SET OF PLANS. 2014 FBC-B 1009.15 |
| | HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE |
| | AND SHALL COMPLY WITH SECTION 1012. |
| | |
| | 1012.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE |
| | NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND |
| | THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF |
| | ONE TREAD BEYOND THE BOTTOM RISER. |
| | |
| | 2014 FBC-ACCESSIBILITY CODE 307.3 POST MOUNTED OBJECTS. |
| | WHERE THE HANDRAIL ON THE OUTER SIDE OF THE STAIRS IS |
| | REQUIRED TO HAVE THE HORIZONTAL EXTENSION OF 12 INCHES |
| | IT WILL NEED TO RETURN UPON ITSELF NO HIGHER THAN 27 |
| | INCHES FOR THE LIMITS OF PROTRUDING OBJECTS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |