| Plan Review Notes For Permit 16120506 |
| Permit Number |
16120506 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-17 04:17:07 | 1) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED NOTES | | | THAT IT IS FOR A SUPPLY PRESSURE OF 11.0 INCHES W.C OR | | | GREATER YET THE GAS RISER SHOWS THE SUPPLY PRESSURE | | | GOING FROM 11INCHES W.C. TO 7 INCHES W.C. AND THEN TO | | | 11 INCHES W.C. CLARIFY. | | | 2) SUBMIT MANUF. SPECS FOR THE NEW RANGE. THE | | | SPECIFICATIONS SHALL SHOW THAT THE RANGE IS LISTED AND | | | LABELED PER 2014 FGC SEC.301.3. | | | 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR.2014 FGC | | | SEC.304. | | | 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE NEW | | | RANGE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|