2016-12-20 13:36:24BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT VERIFY VALUE. PROVIDE FLOOR PLAN OUTLINING
 AREAS OF WORK WITH SQUARE FOOTAGE.
 2. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
 3. STATE TYPE OF UNDERLAYMENT TO BE USED.
 4. PROVIDE THE FOLLOWING ASTM'S FOR THE UNDERLAYMENT
 USED FOR THE INSTALLATION OF ENGINEERED WOOD PRODUCTS -
 ASTM E-84 (FLAME SPREAD), ASTM E-90 (AIORBOURNE SOUND)
 AND E-492 (IMAPCT SOUND).
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49
  
  
  