| 2017-01-12 11:05:24 | JOB PERMIT NUMBER: 16120473 |
| | JOB ADDRESS: 10646 STARLING WAY |
| | WEST PALM BEACH FLORIDA |
| | DATE: JANUARY 12, 2017 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, |
| | (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY |
| | OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF |
| | ITEMS NOTED. |
| | |
| | 1] CLARIFY ON RISER DIAGRAM IF THE FEEDER CONDUIT IS |
| | METALLIC RMC, IMC, OR EMT? IF NOT PLEASE SHOW AN EGC |
| | PER FBC-R SECTION E3908.8. |
| | |
| | 2] PLEASE CORRECT NOTE # 25, FBC-E SECTION 404.1 STATES |
| | A MINIMUM OF 75% OF LAMPS IN PERMANENTLY INSTALLED |
| | LUMINAIRES SHALL BE HIGH EFFICACY LAMPS. |
| | |
| | 3] SINCE GAS APPLIANCES ARE PRESENT PLEASE ADD A NOTE |
| | THEY SHALL BE BONDED IN ACCORDANCE WITH FBC-E SECTION |
| | E3609.7. |
| | |
| | 4] RECESSED LIGHTS INSTALLED IN BUILDING ENVELOPE SHALL |
| | BE SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED & |
| | UN-CONDITIONED SPACES. IN ADDITION IF HOUSING CANS ARE |
| | INSTALLED IN THERMAL INSULATION THEY SHALL BE LISTED |
| | IC-RATED PER FBC-E SECTION R402.4.4, A NOTE WILL |
| | SUFFICE. |
| | |
| | 5] LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT. |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |