Plan Review Notes
Plan Review Notes For Permit 16120462
Permit Number 16120462
Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-12 10:11:28JOB PERMIT NUMBER: 16120462
 JOB ADDRESS: 10543 STARLING WAY
 WEST PALM BEACH FLORIDA
 DATE: JANUARY 12, 2017
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014,
 (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY
 OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF
 ITEMS NOTED.
  
 1] CLARIFY ON RISER DIAGRAM IF THE FEEDER CONDUIT IS
 METALLIC RMC, IMC, OR EMT? IF NOT PLEASE SHOW AN EGC
 PER FBC-R SECTION E3908.8.
  
 2] PLEASE CORRECT NOTE # 25, FBC-E SECTION 404.1 STATES
 A MINIMUM OF 75% OF LAMPS IN PERMANENTLY INSTALLED
 LUMINAIRES SHALL BE HIGH EFFICACY LAMPS.
  
 3] SINCE GAS APPLIANCES ARE PRESENT PLEASE ADD A NOTE
 THEY SHALL BE BONDED IN ACCORDANCE WITH FBC-E SECTION
 E3609.7.
  
 4] RECESSED LIGHTS INSTALLED IN BUILDING ENVELOPE SHALL
 BE SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UN-CONDITIONED SPACES. IN ADDITION IF HOUSING CANS ARE
 INSTALLED IN THERMAL INSULATION THEY SHALL BE LISTED
 IC-RATED PER FBC-E SECTION R402.4.4, A NOTE WILL
 SUFFICE.
  
 5] LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  