2017-01-17 20:09:29NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENT.
 CODE; FBC 5TH EDITION (2014).
  
 1- SHEET CS1: REVISE THE EXPOSURE CATEGORY. ACCORDING
 TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED AND
 REVISE THE DESIGN PRESSURES ON SHEET 6A. ALSO, CLARIFY
 WHY THE DESIGN PRESSURES FOR WINDOW #002 IS -00.00?
  
 2- DETAILS 3 AND 6 OF SHEET 9D DON'T COMPLY WITH THE
 INSPECTION FOR TERMITES CLEARANCE AS REQUIRED BY SEC.
 R318.7 FBC-RESIDENTIAL. REVISE AS REQUIRED TO COMPLY.
  
 3- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENER TYPE AND
 SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) CALCULATIONS SUBMITTED ARE DONE FOR WORST CASE
 SCENARIO. PROVIDE COMPLETE CALCULATIONS FOR EACH
 ORIENTATION AS REQUIRED BY THE EXCEPTION OF SEC.
 R405.4.2 FBC-ENERGY CONSERVATION OR PROVIDE ENERGY
 CALCULATIONS FOR THE ACTUAL ORIENTATION OF THE
 BUILDING.
  
 B) REVISE/CLARIFY DOOR TYPE INFORMATION SHOWN ON PAGE 3
 OF 4. WHERE ARE THE WOOD DOORS. PRODUCT APPROVAL FOR
 ENTRY DOORS IS FOR GLAZED FIBERGLASS DOOR. THIS DOOR
 NEEDS TO BE ENTERED IN THE WINDOW AREA AS REQUIRED BY
 SEC. R405.5.3.3 FBC-ENERGY CONSERVATION.
  
 C) REVISE THE WALL TYPE SPECIFIED ON PAGE 3 OF 4 FOR
 THE GARAGE AREA. ACCORDING TO THE WCI/PLAN STANDARDS ON
 SHEET 6A ALL INTERIOR WALLS ARE METAL NOT WOOD. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) IT LOOKS LIKE THE THE NOTARY PUBLIC IS SIGNING FOR
 THE OWNER ON THE FRONT PAGE OF THE ENERGY CALCULATIONS
 AND FOR THE BUILDER ON THE EPL DISPLAY CARD. ENERGY
 CALCULATIONS MAY BE SIGNED BY AN AGENT LEGALLY
 DESIGNATED BY THE OWNER AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION. PROVIDE PROOF THAT OWNER
 ASSIGNED THIS AGENT.
 ON THE OTHER HAND, WHY IS THE NOTARY PUBLIC SIGNING FOR
 THE BUILDER?. BUILDER NEEDS TO SIGN.
  
 ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  