| Plan Review Notes For Permit 16120416 |
| Permit Number |
16120416 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-01 12:24:06 | PLEASE NOTE THAT THE CALCULATION FOR SUBPANEL SUBMITTED | | | IS 112AMPS, EXISTING PANEL IS RATED AT 100AMP. PANEL | | | SCHEDULE SHOWS A 200 AMP PANEL. AT THIS TIME A COMPLETE | | | SERVICE CALCULATION IS TO BE SUBMITTED REFLECTING THE | | | OVERCURRENT PROTECTION LANDED AT MAIN 200 PANEL FEEDING | | | SUBPANEL LOADS. CALCULATION CANNOT EXCEED RATED BUS | | | SIZE AMP. COORELATE RISER DIAGRAM AND PANEL SCHEDULES | | | TO MATCH ACTUAL INSTALLATION. FBC 107.3.5 | | | | | | V. PEREZ | | | *6717 |
|