Plan Review Notes
Plan Review Notes For Permit 16120416
Permit Number 16120416
Review Stop E
Sequence Number 2
Notes
Date Text
2017-02-01 12:24:06PLEASE NOTE THAT THE CALCULATION FOR SUBPANEL SUBMITTED
 IS 112AMPS, EXISTING PANEL IS RATED AT 100AMP. PANEL
 SCHEDULE SHOWS A 200 AMP PANEL. AT THIS TIME A COMPLETE
 SERVICE CALCULATION IS TO BE SUBMITTED REFLECTING THE
 OVERCURRENT PROTECTION LANDED AT MAIN 200 PANEL FEEDING
 SUBPANEL LOADS. CALCULATION CANNOT EXCEED RATED BUS
 SIZE AMP. COORELATE RISER DIAGRAM AND PANEL SCHEDULES
 TO MATCH ACTUAL INSTALLATION. FBC 107.3.5
  
 V. PEREZ
 *6717