2017-02-15 18:30:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT AND PLANS SPECIFY THAT THIS PROJECT IS AN
 EXISTING COTTAGE THAT WILL BE REMODELED AND HAVE AND
 ADDITION. ALTHOUGH, A PERMIT APPLICATION FOR THIS WORK
 WAS APPLIED FOR, A PERMIT WAS NEVER ISSUED TO CONVERT
 THIS DETACHED GARAGE INTO LIVING SPACE. THERE IS AN
 AFFIDAVIT ON FILE DATED APRIL 29, 2016 THAT STATES THE
 WORK ON THE GARAGE CONVERSION WAS NEVER DONE. ANY WORK
 THAT WAS DONE TO THE DETACHED GARAGE WAS DONE SO
 WITHOUT PERMITS OR INSPECTIONS. PLEASE BE ADVISED THE
 INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO BE
 MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) THIS IS ALSO A CHANGE OF OCCUPANCY WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION. FBC EXISTING BUILDING SECTION
 1001.2
  
 3) THE FRENCH DOOR THAT IS MARKED AS EXISTING DOOR ON
 THE PLANS WAS INSTALLED WITHOUT PERMITS OR INSPECTIONS.
 SUBMIT PRODUCT APPROVALS FOR THIS DOOR FOR REVIEW AS
 REQUIRED BY DCA RULE 9N-3.
  
 4) SUBMIT THE PRODUCT APPROVALS FOR THE WALL LOUVER
 ATTIC VENTS AND PROVIDE DOCUMENTATION OF THE NET FREE
 AREA OF THE VENTS. THE REQUIRED NET VENT AREA IS 3.06
 SQFT. SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED
 OR R806.5 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER
 ASSEMBLIES. FBC R806.1 ENCLOSED ATTICS AND ENCLOSED
 RAFTER SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL HAVE
 CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST
 DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.1.8. REQUIRED VENTILATION OPENINGS SHALL OPEN
 DIRECTLY TO THE OUTSIDE AIR.
  
 5) THE ENERGY COMPLIANCE FORM R405-2014 THAT WAS
 SUBMITTED CONTAINS ERRORS AND OMISSIONS. THIS IS NOT A
 MODEL THAT WILL BE WITH DIFFERENT ORIENTATIONS. THIS IS
 A ONE OF A KIND STRUCTURE AND IT IS SITE SPECIFIC.
 THEREFORE, YOU CAN NOT USE THE WORST CASE ORIENTATION
 ON THE FORM. USE THE ACTUAL ORIENTATION OF THE BUILDING
 FOR ENERGY AND EQUIPMENT SIZING CALCULATIONS. THERE
 WILL BE NO ROTATE ANGLE. THERE IS NO KITCHEN ( NOT
 ALLOWED BY ZONING REGULATIONS ). FBC 107.2.1
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FRENCH DOORS HAS A NEGATIVE DESIGN PRESSURE THAT IS NOT
 ADEQUATE. THE PLANS REQUIRE +37.8, - 50.6 PSF AND THE
 PRODUCT IS RATED FOR +45, -45 PSF. FBC-R 301.2.1
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 ROOFING MATERIAL THAT WILL BE INSTALLED ON THE FLAT
 ROOF.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  