| 2016-12-15 17:21:17 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | (1) PROVIDE RETURN AIR FOR BEDROOM. RETURN AIR CANNOT |
| | BE THROUGH A BEDROOM. |
| | (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | (3) PROVIDE APPROVED HEAT LOAD CALCULATION. HEAT LOAD |
| | SUMMARY CAN BE ADDED IN ADDITION BUT CANNOT TAKE THE |
| | PLACE OF A HEAT LOAD CALCULATION. |
| | |
| | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN |
| | SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER |
| | SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR |
| | OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM |
| | SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY |
| | LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS |
| | STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. |
| | |
| | |
| | JORGE VALIDO |
| | WPB MECHANICAL INSPECTOR/PLANS EXAMINER |