Plan Review Notes
Plan Review Notes For Permit 16120416
Permit Number 16120416
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-15 17:21:17CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE RETURN AIR FOR BEDROOM. RETURN AIR CANNOT
 BE THROUGH A BEDROOM.
 (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) PROVIDE APPROVED HEAT LOAD CALCULATION. HEAT LOAD
 SUMMARY CAN BE ADDED IN ADDITION BUT CANNOT TAKE THE
 PLACE OF A HEAT LOAD CALCULATION.
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR
 OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM
 SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY
 LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS
 STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved